Alarm Conditions

1 1 0 0 . . 6 6 A A l l a a r r m m C C o o n n d d i i t t i i o o n n s s
Table 29. Typical Alarm Conditions
Code
Alarm/ Notice/
Command/Status
0
INPUT AC OVER
VOLTAGE
1
INPUT AC UNDER
VOLTAGE
2
INPUT AC OVER
FREQUENCY
3
INPUT AC UNDER
FREQUENCY
64
Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User's Guide P-164000906—Rev 05
Typical Alarm Conditions
Alarm (A)
What it Means
Notice (N)
N
UPS measuring higher
than input voltage
maximum
N
UPS measuring lower
than input voltage
minimum
N
UPS measuring higher
than input frequency
maximum
N
UPS measuring lower
than input frequency
minimum
UPS Status
Recommended
Troubleshooting Steps
Battery Mode supporting
If UPS is in Battery Mode,
Load Or Keep-Alive Mode
that is expected behavior If
and not supporting load
UPS is in Keep-Alive Mode:
Check Input Circuit Breaker
(CB) if it is Off. If it is Off,
check AC Input Source and
make sure it is compatible
with the UPS' ratings. If
input AC Source measures
good, turn the Input CB ON.
If problem persists, call
Eaton Service
Battery Mode supporting
If UPS is in Battery Mode,
Load Or Keep-Alive Mode
that is expected behavior If
and not supporting load
UPS is in Keep-Alive Mode:
Check Input Circuit Breaker
(CB) if it is Off. If it is Off,
check AC Input Source and
make sure it is compatible
with the UPS' ratings. If
input AC Source measures
good, turn the Input CB ON.
If problem persists, call
Eaton Service
Battery Mode supporting
If UPS is in Battery Mode,
Load Or Keep-Alive Mode
that is expected behavior If
and not supporting load
UPS is in Keep-Alive Mode:
Check Input Circuit Breaker
(CB) if it is Off. If it is Off,
check AC Input Source and
make sure it is compatible
with the UPS' ratings. If
input AC Source measures
good, turn the Input CB ON.
If problem persists, call
Eaton Service
Battery Mode supporting
If UPS is in Battery Mode,
Load Or Keep-Alive Mode
that is expected behavior If
and not supporting load
UPS is in Keep-Alive Mode:
Check Input Circuit Breaker
(CB) if it is Off. If it is Off,
check AC Input Source and
make sure it is compatible
with the UPS' ratings. If
input AC Source measures
good, turn the Input CB ON.