The Eaton FERRUPS FX UPS selects the appropriate operating mode automatically; however, there may be times when you
need to set the operating mode manually from the control panel.
The names of the Eaton FERRUPS FX control features are located in yellow at the bottom of the Remote
Control Display keys. You can change the operating mode by pressing the [CONTROL] button followed by the
number that describes the operating mode.
UPS Operating Mode Commands
Table 14. UPS Operating Mode Commands
Operating Mode
Off
Auto
Line Condition
Inv On
Additional Control Commands
Table 15. Additional Control Commands
Alarm
Chgr (Battery Charger)
User Test Alarm
How to Select It
Press [CONTROL] —1 [ENTER] [ENTER]
Press [CONTROL] —2 [ENTER] [ENTER]
Press [CONTROL] —3 [ENTER] [ENTER]
Press [CONTROL] —4 [ENTER] [ENTER]
Additional Control Functions
Press [CONTROL] —5 [ENTER] [ENTER]
Press [CONTROL] —6 [ENTER] [ENTER]
Press [CONTROL] —8 [ENTER] [ENTER]
Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User's Guide P-164000906—Rev 05

Changing Operating Modes

What It Means
The UPS does not provide power to your
equipment, but you can still use the
control panel if DC power is present. The
READY indicator is off.
This is the normal operating mode for the
FX UPS. The UPS conditions AC input
power and provides the conditioned
power to your equipment. The AC LINE
and READY indicators should be
illuminated in this mode.
The UPS is conditioning the AC input
power and providing the conditioned
power to your equipment, but if there is
power outage the UPS does not switch to
battery power. Instead, the UPS shuts
down output until AC input power is
available again. The READY indicator will
blink and the AC LINE indicator is on
when the UPS is in this mode.
The UPS converts battery power to AC
power for your equipment. It does not
charge the batteries. the On Batt
indicator is on. The READY indicator is
off.
Permanently enables and disables the
alarm beeper.
Enables and disables the UPS internal
charger.
Initiates a User Test Alarm ( Can be
cleared by pressing [CONTROL] —8
[ENTER] [ENTER], or by pressing Press
[CONTROL] —0 [ENTER] [ENTER])