4.8 Capacitor Changing Control at Optimal Control Operation
■
Optimal control is suitable for circuits with sharp load fluctuation. However
decreases gradually when multiple capacitors are closed
,
capacity
and the capacitor with the largest capacity will remain last.
■
In the area where light load disconnection is not made
the capacity. Thus this last capacitor will not be cut off.
■
When the power factor leads out further than
control takes place where large capacity capacitor opens and small capacity capacitor closes.
Setting value of Target Power Factor is not 100 %.
EXPORT
Setting value of Target Power Factor is 100 %.
EXPORT
95
Changing Area
LEAD
LEAD OUT
LAG OUT
LAG
Light Load Disconnection Level
Changing Area
LEAD
LAG
Light Load Disconnection Level
19
,
capacitors will open from the smallest
,
the disconnection level is determined by
% (Changing Area) in this status
LEAD 95 % Level
Disconnection Level
Active Power
PROPER
Connection Level
LEAD 95 % Level
LEAD OUT
Disconnection Level
PROPER
Connection Level
Active Power
LAG OUT
,
in case the load
,
changing