Cable Clamp Fitting - Mitsubishi Electric MELSERVO EMC Installation Manuallines

Ac servo system
Hide thumbs Also See for MELSERVO EMC:
Table of Contents

Advertisement

4.4

Cable clamp fitting

Generally, connecting the grounding wire of the shielded wire to the SD terminal of the connector provides a sufficient effect.
However, the effect can be increased when the shielded wire is connected directly to the ground plate as shown below. Install
the ground plate near the servo amplifier for the encoder cable. Peel part of the cable insulator to expose the external
conductor, and press that part against the ground plate with the cable clamp. If the cable are thin, bunch several cables
together and clamp them in place.
The cable clamp comes as a set with the grounding plate.
[Unit: mm]
Clamp fittings
(A, B)
Clamp section diagram
• Dimensions
[Unit: mm]
Grounding plate
2-φ5 hole
17.5
Mounting hole
6
22
*1
M4 screw
35
*1 Screw hole for grounding. Connect it to the ground plate of the cabinet.
Model
AERSBAN-DSET
AERSBAN-ESET
Clamp fitting
A
B
Precautions
• The motor cable (single cable type) has no shield on the outermost circumference. Therefore, to ground the motor cable
with a cable clamp, use a motor cable (dual cable type).
4 EMC COUNTERMEASURE PARTS
20
4.4 Cable clamp fitting
Strip the cable insulator
of the clamped area
Cable
Grounding plate
External conductor
Clamp fitting
L or less
A
100
70
Cutter
Cable
10
B
C
86
30
56
L
70
45
Accessory fittings
Clamp A: 2 pcs.
Clamp B: 1 pc.