Viessmann VIESMANN VITOLIGNO 300-H Technical Manual page 27

Boiler for automatic charging with pellets and woodchips
Table of Contents

Advertisement

Ecotronic control unit for Vitoligno 300-H
Differences between the extension kits listed below
■ Part no. ZK01 270
– For direct connection to the Ecotronic
– For systems without solar thermal installation:
For heating circuit 1 with mixer and heating circuit 2 with mixer,
direct control by the Ecotronic
– For systems with solar thermal installation:
For heating circuit 1 with mixer, direct control by the Ecotronic
■ Part no. 7301 062, Part no. 7301 063
Extension kits with mixer PCB
– For connection via KM BUS
Information on extension kit, part no. ZK01 270
For DHW heating, the following must be ordered separately: The
"temperature sensor set for the solar circuit", part no.: ZK01 271 is
used as a cylinder temperature sensor for DHW heating (only one
sensor is required). The contact temperature sensor included in the
extension kit delivery is not required.
Mixer extension kit with integral mixer motor
Part no. ZK01 270
For wiring on site.
Components:
■ Mixer motor
■ Flow temperature sensor as contact temperature sensor (Pt1000)
■ For Viessmann heating mixers DN 20 to 50 (welding fitting) and R
½ to 1¼ (not for flanged mixers).
■ For systems without solar thermal system: For heating circuits 1 and
2 with mixer, directly controlled by the Ecotronic.
■ For systems with solar thermal system: For heating circuit 1 with
mixer, directly controlled by the Ecotronic.
The mixer motor is mounted directly onto the Viessmann mixer DN 20
to 50 and R ½ to 1¼.
Mixer motor
0
1 8
Specification
Rated voltage
Rated frequency
Power consumption
IP rating
Safety category
Permissible ambient temperature
– During operation
– During storage and transport
Torque
Runtime for 90 ° ∢
VITOLIGNO 300-H
(cont.)
230 V~
50 Hz
4 W
IP 42 to EN 60529
Ensure through design/instal-
lation
II
0 to +40 °C
–20 to +65 °C
3 Nm
120 s
Flow temperature sensor (contact temperature sensor)
4 2
6 6
Secured with a tie.
Specification
Cable length
IP rating
Sensor type
Safety category
Sensor type
Permissible ambient temperature
– During operation
– During storage and transport
Information on extension kit, part no. 7301 063
For DHW heating, the following must be ordered separately:
For DHW heating, the temperature sensor with part no. 7438 702 is
used as a cylinder temperature sensor (sensor well to be ordered sep-
arately if required).
The contact temperature sensor, which is part of the extension kit
delivery, is used as a return temperature sensor.
Mixer extension kit with integral mixer motor
Part no. 7301 063
KM BUS subscriber
Components:
■ Mixer PCB with mixer motor for Viessmann mixer DN 20 to 50 and
R ½ to 1¼
■ Flow temperature sensor (contact temperature sensor)
■ Plug for connecting the heating circuit pump
■ Power cable (3.0 m long) with plug
■ BUS cable (3.0 m long) with plug
The mixer motor is mounted directly onto the Viessmann mixer DN 20
to 50 and R ½ to 1¼.
Mixer PCB with mixer motor
0
1 8
5.0 m, fully wired
IP 42 to IEC 60529
Viessmann Pt1000
III to EN 60730
QAD2012 (Pt1000)
–5 to +50 °C to
IEC 60721-3-3
–25 to +70 °C to
IEC 60721-3-2
1 3
0
VIESMANN
27
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents