12J : Amber LED will remain ON continously indicating that the fault is cleared
12K : Press the Green ON push button to switch ON the starter.
12L : Starter gets switched ON.
12M: Green LED turns ON indicating that the starter is ON.
12N : Delivery tank gets filled till the water touches the level of P3 sensor.
Table: 23 Range of Under voltage & Over voltage
Starter
Voltage Range
undervoltage fault
(V)
Manual
(Z6) 200-400
(Z8) 260-460
(R0) 323-457
(Q0) 304-418
2) LMR-A: Manual mode
b. WLCA- Suction mode
12A
: Check the mode of LMR-A, if it is manual mode.
12B
: Check the mode of WLCA, if it is suction mode.
12C to 12M : Follow steps from 12C to 12M of Manual & Delivery mode .Refer corrective action 1 of Table
22. (except the 6Note).
12N
: Water gets drawn out of the suction tank till the water level goes below P2 sensor.
Note
: Amber LED willnot blink or provide any indication for the misplacement of sensors in the
6
suction tank. Please follow the below steps for the corrective action of any fault which may arise due
to the misplacement of sensors in the suction tank.
12H: Check if the P1,P2, P3 sensors of delivery tank are out of water.
6
12I : If yes, then keep P1, P2, P3 sensors in water for operating the starter.
6
3) LMR-A: Manual mode
c. WLCA- Dual tank mode
12A
: Check the mode of LMR-A, if it is manual mode.
12B
: Check the mode of WLC-A, if it is dual tank mode.
12C to 12M : Follow steps from 12C to 12K of Manual & Delivery mode Refer corrective action 1 of Table
22. (except the 6Note).
Note
: Amber LED willnot blink or provide any indication for the misplacement of sensors in the Delivery &
6
suction tank. Please follow the below steps for the corrective action of any fault which may arise due to
the misplacement of sensors in the delivery tank.
12H
: Check if the P1,P2, P3 sensors of suction tank are out of water or P5,P6 sensors of delivery tank in water.
6
12I
: If yes, then keep P1, P2, P3 sensors in water & P5, P6 sensors out of water for operating the starter.
6
Undervoltage fault
Trip voltage for
Healthy voltage
(V)
195
250
313
294
Trip voltage for
Overvoltage fault
(V)
205
260
323
304
Overvoltage fault
Healthy voltage
(V)
400
455
457
418
(V)
390
445
447
408
20