Mitsubishi 900 Series User Manual page 94

Graphic operation terminal
Hide thumbs Also See for 900 Series:
Table of Contents

Advertisement

2) Precautions for manufacturing cable
• Make a twisted pair for each signal and SG.
• Connect the braided shield to the connector shell (both ends).
• The cable used for the Mitsubishi EMC Directive compatibility test had the following
specifications.
Item
Cable type
Conductor section area (mm
3) Connector (connector cover)
• GOT connector
Use the connector matching the following model for the GOT.
9-pin D-sub (male) inch screw type
manufactured by DDK
17JE-23090-27 (D3CC)
• Connector of computer link unit
Refer to the user's manual of the serial communication, computer link module or PLC CPU
with computer link function.
4) Cable production method
• Peel the sheath (with the length shown below) at both ends of the cable, and expose the
shield braided wire for grounding.
• The cable must be 15m or shorter.
GOT side
130
(5.12)
Within 230
40
(9.06)
(1.57)
8.3 Wiring Precautions the Part which Matches the EMC Directives
Twisted pair shield cable
2
0.2
)
Ferrite core
(ZCAT3035-1330)
40
(1.57)
8.3.2 Grounding the ground cable
Specification
Computer link module side
130
(5.12)
Within 400
Unit: mm (inch)
(15.75)
1
2
3
4
5
6
7
8
8 - 16

Hide quick links: