BE/SIG

This output is the value of the binary signal, after all internal processing, that is
available for further processing in logic.

BE/SIGN

This is the value of the inverted binary signal, after all internal processing, that is
available for further processing in logic.

KSIM

This is the simulation indication output. It will be high (logic "1") when the signal is
being simulated.

KG

This is the channel valid signal output. It will be high (logic "1") as long as the
channel is valid (Internal monitoring logic determines the validity of the signal).
GT
This parameter defines which type of sensor is connected to the SIM module.
There are 7 possible choices in the parameter mask: 0,1,2,3, 4, 5, and 6.
Meaning:
0. No sensor type
1. Form C contact with 47k ohm bridging resistor
2. Form C contact without 47k ohm bridging resistor
3. Form A or B contact with 47k ohm bridging resistor
4. Form A or B contact without 47k ohm bridging resistor
5. Three-wire proximity switch (FUM application)
6. Four-wire proximity switch (FUM application)
The default setting is 4