Emerson Rosemount 3051 Quick Start Manual page 16

Pressure transmitter and dp flowmeters with wirelesshart protocol
Hide thumbs Also See for Rosemount 3051:

Advertisement

Quick Start Guide
International
I7
IECEx Intrinsic Safety
Certificate: IECEx BAS 12.0124X
Standards: IEC 60079-0: 2011, IEC 60079-11: 2011
Markings: Ex ia IIC T4 Ga, T4(-40 °C ≤ T
IP66/IP68
Special Conditions for Safe Use (X):
1. The plastic enclosure may constitute a potential electrostatic ignition risk and
must not be rubbed or cleaned with a dry cloth.
2. The Model 701PGNKF Power Module may be replaced in a hazardous area. The
power module has a surface resistivity greater than 1GΩ and must be properly
installed in the wireless device enclosure. Care must be taken during
transportation to and from the point of installation to prevent electrostatic
charge build-up.
Brazil
I2
INMETRO Intrinsic Safety
Certificate: UL-BR013.0534X
Standards: ABNT NBR IEC60079-0:2008, ABNT NBR IEC60079-11:2009
Markings: Ex ia IIC T4 IP66 Ga, T4(-40 °C ≤ T
IP66/IP68
Special Condition for Safe Use (X):
1. See certificate for special conditions
China
I1
China Intrinsic Safety
Certificate: GYJ101312X [Flowmeters]
Standards: GB3836.1-2000, GB3836.4-2000
Markings: Ex ia IIC Ga T46
Special Condition for Safe Use (X):
1. See certificate for special conditions.
EAC - Belarus, Kazakhstan, Russia
IM
Technical Regulation Customs Union (EAC) Intrinsic Safety
Certificate: RU C-US.ГБ05.B.00400
Markings: 0Ex ia IIC T4 Ga X;
Special Condition for Safe Use (X):
1. See certificate for special conditions.
16
≤ +70 °C)
a
≤ +70 °C)
a
May 2015