Siemens SITRANS P Operating Instructions Manual page 205

Pressure transmitter
Hide thumbs Also See for SITRANS P:
Table of Contents

Advertisement

Absolute pressure measuring limits from dif‐
ferential pressure series
For process temperature 60 °C < ϑ
≤ 100 °C (max. 85 °C for measur‐
ing cell 30 bar) (140 °F < ϑ ≤ 212 °F
(max. 185 °F for measuring cell
435 psi))
Upper measuring limit
Lower range value
SITRANS P320/P420 with 4 to 20 mA/HART
Operating Instructions, 11/2019, A5E44852162-AC
30 mbar a + 20 mbar a • (ϑ - 60 °C)/°C
3 kPa a + 2 kPa a • (ϑ - 60 °C)/°C
0.44 psi a + 0.29 psi a • (ϑ - 140 °F)/°F
100% of max. range (for oxygen measurement: max. 100 bar/10 MPa/
1450 psi and 60 °C ambient temperature/medium temperature)
Between the measuring limits (continuously adjustable)
Technical data
13.1 Input
205