Diagnosis and correction with multi-boiler systems
Fault
The boiler does not start up
The burner does not switch on
Cause
Heating system switch "8" turned
to OFF on the control unit
Electrical isolator switch,
if installed, is switched off
Fuse in the domestic power circuit or
in the control unit has blown or
tripped
No request from the master control
Heating program "9" is set (the
corresponding button is illuminated)
Vitoair draught stabilizer defective
(only on boilers with pressure jet
burner)
Failure of motor-controlled flue gas
damper (only on gas boilers with
atmospheric burner)
Fault on control unit
No fuel
Troubleshooting guide
Remedy
Switch on
Switch on electrical isolator switch
Inform heating contractor
Check the settings on he master
control
Set "rw" heating program
(page 6)
Inform heating contractor.
Change setting of Vitoair to
manual operation:
Press in rotary knob A on
motor and turn fully beyond
setting "4".
Inform heating contractor.
Change setting of motor-controlled
flue gas damper to manual operation:
Press in rotary knob A on motor
and turn fully beyond setting "4".
After consulting your heating con-
tractor, the boiler can be operated
temporarily with constant boiler
water temperature by turning the
emissions test switch "S" to "h";
leave cover open
Oil or LPG:
Check fuel supply and re-order if
necessary.
Natural gas:
Open gas-shut off valve or contact
gas supply company if necessary.