Specifications - Fujitsu AUYG18LVLB Design & Technical Manual

Cassette type
Hide thumbs Also See for AUYG18LVLB:
Table of Contents

Advertisement

1. Specifications

Type
Model name
Power supply
Available voltage range
Rated
Cooling
Min.—Max.
Capacity
Rated
Heating
Min.—Max.
Rated
Cooling
Max.
Input power
Rated
Heating
Max.
Cooling
Current
Rated
Heating
Cooling
Power factor
Heating
EER
Cooling
COP
Heating
Moisture removal
Cooling
Maximum operating current *1
Heating
Cooling
Airflow rate
Fan
Heating
Type × Q'ty
Motor output
Cooling
Sound pressure level *2
Heating
Cooling
Sound power level
Heating
Dimensions (H × W × D)
Fin pitch
Heat exchanger type
Rows × Stages
Pipe type
Fin type
Net
Dimensions
(H × W × D)
Gross
Net
Weight
Gross
Liquid
Size
Connection
Gas
pipe
Method
Cooling
Operation range
Heating
Material
Color
Dimensions
Cassette grille
(H × W × D)
(Option)
Weight
Remote controller
Material
Drain hose
Size
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: Maximum current:
– The maximum value when operated within the operation range.
– The total current of indoor unit and outdoor unit.
• *2: Sound pressure level:
– Measured values in manufacturer's anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
kW
Btu/h
kW
Btu/h
kW
Btu/h
kW
Btu/h
kW
A
%
kW/kW
L/h (pints/h)
A
HIGH
MED
LOW
QUIET
3
m
/h
HIGH
MED
LOW
QUIET
W
HIGH
MED
LOW
QUIET
dB (A)
HIGH
MED
LOW
QUIET
HIGH
dB (A)
mm
mm
kg
mm (in)
°C
%RH
°C
Net
mm
Gross
Net
kg
Gross
mm
- 2 -
Cassette
Inverter heat pump
AUYG18LVLB
230 V ~ 50 Hz
198—264 V
5.20
17,700
0.90 - 5.90
3,100 - 20,100
6.00
20,500
0.90 - 7.50
3,100 - 25,600
1.62
2.04
1.66
2.83
7.2
7.4
97.8
97.5
3.21
3.61
2.2 ( 3.9 )
11.5
13.5
680
580
490
410
800
680
580
450
Turbo × 1
54
38
34
30
26
43
38
34
30
50
55
210 × 1,310 × 13.3
210 × 1,250 × 13.3
1.2
2 × 10
Copper tube
Aluminum
245 × 570 × 570
265 × 730 × 625
15
18
Ø 6.35 (Ø 1 / 4 in.)
Ø12.70 (Ø1/2 in.)
Flare
18 to 32
80 or less
16 to 30
Hi-PS
White Approximate color of Munsell N 9.25 /
49 × 700 × 700
120 × 765 × 755
2.6
4.5
Wireless [Wired (option)]
PVC
VP25 [Ø25(I.D.),Ø32(O.D.)]
AUYG24LVLA
6.80
23,200
0.90 - 8.00
3,100 - 27,300
8.00
27,300
0.90 - 9.10
3,100 - 31,000
2.21
2.85
2.26
3.19
9.7
9.9
99.1
99.3
3.08
3.54
2.7 ( 4.8 )
14.7
15.7
930
830
600
450
930
860
700
530
49
44
36
30
49
45
40
33
59
61
210 × 1,360 × 13.3
210 × 1,295 × 13.3
210 × 1,235 × 13.3
1.45
3 × 10
16
19
Ø15.88 (Ø5/8 in.)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Auyg24lvlaAoyg18lbcbAoyg24lbcb

Table of Contents