8. External input and output

Connector
CN102
Control input (Operation/Stop)
CN103
CN6

8-1. External input

• "Operation/Stop" mode or "Forced stop" mode can be selected with function setting of indoor
unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
¢ Control input (Operation/Stop or Forced stop)
The air conditioner can be remotely operated by means of the following on-site work.
Unit operation is started at the following contents by adding the contact input of a commercial
on/off switch to a connector on the external control PCB and turning it on.
Unit operation
Operation mode
Set temperature
Airflow mode
Air direction (swing)
Input
Operation status output
Fresh-air control output
Initial setting after power is on
Auto changeover
24 °C
AUTO
Standard air direction (swing OFF)
- 18 -
Output
See external input/output
settings for details.
Starting mode other than initial
setting
Mode at previous operation
Temperature at previous operation
Mode at previous operation
Air direction at previous operation
Remarks