Parameter
V1s
V2s
Qs limit
V1i
V2i
Qi limit
T Delay
Lock-in power
Lock-out power
Menu item path
Main Menu > Active/Reactive Pwr > Reactive Power Ctrl
> Q(V)
Calling up the menu item
1 0 . N o v 2 0 1 9 1 5 : 3 2
S t a t u s :
O n G r i d
P o w e r :
E - T o d a y :
I n v e r t e r I n f o .
G e n e r a l S e t t i n g s
I n s t a l l S e t t i n g s
A c t i v e / R e a c t i v e P w r
F R T
W a r n i n g :
A d j . w o u l d a f f e c t
e n e r g y p r o d u c t i o n .
P a s s w o r d
0 * * *
A c t i v e P o w e r C t r l
R e a c t i v e P o w e r C t r l
C o n s t a n t c o s p h i
C o s p h i ( P )
C o n s t a n t Q
Q ( V )
Installation and Operation Manual for Power Inverter RPI M6A M8A M10A EU V4 EN 2020-07-13
Description
The lower voltage limit for feeding inductive reactive power.
The upper voltage limit for feeding inductive reactive power.
The limit value for inductive reactive power. The value is set as a per-
centage of the nominal apparent power Sn. This value is connected
to the parameter V2s.
The upper voltage limit for feeding capacitive reactive power.
The lower voltage limit for feeding capacitive reactive power.
The limit value for capacitive reactive power. The value is set as a
percentage of the nominal apparent power Sn. This value is con-
nected to the parameter V2i.
Delay time before feeding reactive power.
The upper limit of the active power range in which the function is
active. The value is set as a percentage of the nominal active power.
The lower limit of the active power range in which the function is
active. The value is set as a percentage of the nominal active power.
1.
When the default information is displayed, press any button to open the main menu.
Otherwise, press the
0 W
0 k W h
2.
Use the
the button
ENT
3.
This function is protected with password 5555.
Use the
Press the
ENT
4.
Use the
button.
ENT
5.
Use the
button repeatedly until the main menu is displayed.
ESC
and
buttons to select the Active/Reactive Pwr entry and then press
.
and
buttons to set the individual numerals.
button to confirm a numeral.
and
buttons to select the Reactive Power Ctrl and then press the
and
buttons to select the Q(V) entry and then press the
8 Settings
"Active/reactive power" menu area
Setting range
220.0 .. 292.0 V
220.0 .. 292.0 V
ind 63% .. 1% | 0%
184.0 .. 254.0 V
184.0 .. 254.0 V
cap 63% .. 1% | 0%
0 .. 120 s
0 .. 100%
0 .. 100%
button.
ENT
119