Storage Instructions; Qualified Personnel; Preparing For Installation - Siemens XJ-L Busway System Storage, Installation And Maintenance Instructions

Advertisement

1.0 Definitions

1.1 QUALIFIED PERSONNEL

FOR THE PURPOSE OF THIS MANUAL AND
PRODUCT LABELS, QUALIFIED PERSONNEL
IS ONE WHO IS FAMILIAR WITH THE
INSTALLATION, CONSTRUCTION AND
OPERATION OF THE EQUIPMENT AND THE
HAZARDS INVOLVED. IN ADDITION, HE OR
SHE HAS THE FOLLOWING QUALIFICA-
TIONS:
(a) Is trained and authorized to energize, de-energize,
clear, ground and tag circuits and equipment in
accordance with established safety practices.
(b) Is trained in the proper care and use of protective
equipment such as rubber gloves, hard hat, safety
glasses or face shields, flash clothing, etc., in
accordance with established safety practices.
(c) Is trained in rendering first aid.
1.2 DANGER
FOR THE PURPOSE OF THIS MANUAL AND PRODUCT
LABELS, DANGER INDICATES AN IMMINENTLY HAZ-
ARDOUS SITUATION WHICH, IF NOT AVOIDED, WILL
RESULT IN DEATH OR SERIOUS INJURY.
1.3 WARNING
FOR THE PURPOSE OF THIS MANUAL AND PRODUCT
LABELS, WARNING INDICATES A POTENTIALLY
HAZARDOUS SITUATION WHICH, IF NOT AVOIDED,
COULD RESULT IN DEATH OR SERIOUS INJURY.
1.4 CAUTION
FOR THE PURPOSE OF THIS MANUAL AND PRODUCT
LABELS, CAUTION INDICATES A POTENTIALLY
HAZARDOUS SITUATION WHICH, IF NOT AVOIDED, MAY
RESULT IN MINOR OR MODERATE INJURY.

2.0 Storage Instructions

Upon receipt, immediately inspect busway components
for possible concealed damage from shipping and/or
handling. If damage has occurred, file a claim with the
carrier. If there is no damage, restore the packing to its
original condition to prepare for job site storage.
Store busway indoors in a clean and dry area. Protect
against mechanical damage and exposure to lime dust
(concrete), water, corrosive fumes or liquids and salts.
Failure to properly store and protect the busway can
cause damage and will void the warranty.

3.0 Preparing for Installation

Deliver busway to installation location before unpacking.
Shipping crates/cartons contain exterior identification of
the packaged busway components. Each busway com-
ponent is further identified by an item number located
on the nameplate, which corresponds to that same item
number on the busway installation drawing(s).
Inspect each busway component for possible damage.
Consult the factory. Confirm that contact surfaces are
not damaged and are clean and dry. Abrasives should
not be used on these surfaces because contact surfaces
are electroplated. Inspect joint insulators for cracking or
any sign of damage.
Megger each busway component at 1000 volts, phase
to phase and phase to ground, to verify insulation
integrity. Minimum readings should be no less than:
Megohms = 200 / length of run in feet
= 66 / length of run in meters
If readings are below this minimum, do not apply power
to the installed busway and contact Siemens.