Carrier WeatherExpert 48N2 Controls, Start-Up, Operation, Service, And Troubleshooting page 204

Packaged rooftop cooling units with gas heat, optional electric heat, or hydronic heat and comfortlink controls version 10.x
Table of Contents

Advertisement

ITEM
ALLM (cont)
ALERT LIMIT CONFIG. (cont)
DISP (cont)
DISPLAY CONFIGURATION (cont)
PASS
Service Password
S.VFD
SUPPLY FAN VFD CONFIG
N.VLT
VFD1 Nominal Motor Volts
N.AMP
VFD1 Nominal Motor Amps
N.FRQ
VFD1 Nominal Motor Freq
N.RPM
VFD1 Nominal Motor RPM
N.PWR
VFD1 Nominal Motor HPwr
M.DIR
VFD1 Motor Direction
ACCL
VFD1 Acceleration Time
DECL
VFD1 Deceleration Time
SW.FQ
VFD1 Switching Frequency
E.VFD
EXHAUST FAN VFD CONFIG
N.VLT
VFD2 Nominal Motor Volts
N.AMP
VFD2 Nominal Motor Amps
N.FRQ
VFD2 Nominal Motor Freq
N.RPM
VFD2 Nominal Motor RPM
N.PWR
VFD2 Nominal Motor HPwr
M.DIR
VFD2 Motor Direction
ACCL
VFD2 Acceleration Time
DECL
VFD2 Deceleration Time
SW.FQ
VFD2 Switching Frequency
FLTC
FILTER CONFIGURATION
FS.FT
Filter Stat. Fault Timer
F.NOT
Filter Notification Cut
F.ALT
Filter Alert Cutoff
MFL.S
Main Filter Status Cfg.
MF.TY
Main Filter Type
MF.FR
Main Filter Final Resis.
MF.LT
Main Filter Life
MF.RM
Main Filter Reminder
MF.RS
Reset Main Filter Sched.
MF.ST
Main Filter Status
MFT.R
Reset MFT Table Entries?
PFL.S
Post Filter Status Cfg.
PF.TY
Post Filter Type
PF.FR
Post Filter Final Resis.
PF.LT
Post Filter Life
PF.RM
Post Filter Reminder
PF.RS
Reset Post Filter Sched.
PF.ST
Post Filter Status
PFT.R
Reset PFT Table Entries?
PROG
PROGNOSTICS CONFIG.
LQ.SN
Liquid Sensors Installed
P.SPE
Prognostics SP Enable
PG.SP
Prognostics SP Deadband
P.BPE
Prognostics BP Enable
PG.BP
Prognostics BP Deadband
AC.DB
EXV Superheat Deadband
AC.SP
Auto-Comp Suct.Pres Drop
AC.DS
Auto-Comp DS SP Drop
ML.DR
MLV/HGBP DP Drop
AC.CL
Low Charge Alert Cutoff
AC.CH
High Charge Alert Cutoff
AC.MS
Min Charge SST
AC.EC
Economizer Deadband Temp
*
The display text changes depending on the remote switch configuration
(Configuration  UNIT  RM.CF). If RM.CF is set to 0 (No Remote
Switch), then the display text will be "On" or "Off." If RM.CF is set to 1
(Occupied/Unoccupied Switch), then the display text will be "Occupied"
or "Unoccupied." If RM.CF is set to 2 (Start/Stop), then the display text
will be "Stop" or "Start." If RM.CF is set to 3 (Override Switch), then the
display text will be "No Override" or "Override."
APPENDIX A — LOCAL DISPLAY TABLES (CONT)
MODE — CONFIGURATION (cont)
EXPANSION
0000 to 9999
Disable/Enable
Disable/Enable
RANGE
UNITS
CCN POINT
PASSWORD
0 to 999
Voltage
VFD1NVLT
0 to 999
AMPS
VFD1NAMP
10 to 500
VFD1NFRQ
50 to 30000
VFD1NRPM
0 to 500
VFD1NPWR
0 to 1
VFD1MDIR
0 to 1800
Seconds
VFD1ACCL
0 to 1800
Seconds
VFD1DECL
0 to 3
VFD1SWFQ
0 to 999
Voltage
VFD2NVLT
0 to 999
AMPS
VFD2NAMP
10 to 500
VFD2NFRQ
50 to 30000
VFD2NRPM
0 to 500
VFD2NPWR
0 to 1
VFD2MDIR
0 to 1800
Seconds
VFD2ACCL
0 to 1800
Seconds
VFD2DECL
0 to 3
VFD2SWFQ
0 to 10
Minutes
20 to 50
0 to 20
0 to 5
0 to 9
0 to 10
0 to 60
0 to 60
No/Yes
0 to 100
%
No/Yes
MFTRESET
0 to 5
0 to 6
0 to 10
0 to 60
0 to 60
No/Yes
0 to 100
%
No/Yes
No/Yes
PG_SP_EN
0 to 5
"H20
PG_SP_DB
PG_BP_EN
0 to 1
"H20
PG_BP_DB
0 to 2
^F
AC_SH_DB
0 to 10
^F
AC_SP_DR
0 to 10
^F
0 to 2
^F
AC_MLVDR
-10 to 0
^F
AC_CH_LO
0 to 10
^F
20 to 100
^F
AC_SST_M
0 to 10
AC_EC_DB
204
DEFAULT
1111
460*
55.0*
60
1750
40*
0
30
30
2
460*
28.7*
60
1750
20*
0
30
30
2
FS_FT
2
FS_NOTIF
25
FS_ALERT
10
FLTS_ENA
0
MF_TY
0
MF_FR
1
MF_LT
12
MF_RM
10
MF_RS
No
MF_STAT
0
No
PFLS_ENA
0
PF_TY
0
PF_FR
1
PF_LT
12
PF_RM
10
PF_RS
No
PF_STAT
0
PFTRESET
No
LQ_SENS
No
Disable
0.25
Disable
0.05
2
3
AC_DS_SP
2.5
5
-3
AC_CH_HI
1
40
5.0
PAGE NO.
99
99
99
99
99
99
99
99
99
99
98,99
98,99
99
99
99
99
99
99
99
72,73
42,73
72
72
72
72
72
73
42,73
73
73
73
73
73
73
131
126
126
127
127