Daikin GYEQ20AN Service Manual page 96

Gas heat pump air conditioner heat recovery r-410a 50 hz
Table of Contents

Advertisement

Test Run Manual
2 How to Perform a Test Run
4. Alarm/warning history
(1) Enter STOP mode, select CH [4] at Level 1 and press
warning (refer to the table below) at level 2 and press
are displayed alternately.
CH
01
1st most recent warning
02
2nd most recent warning
:
12
12th most recent warning
Problems during Operation
When the "run lamp" and "inspection indicator" of the remote controller blinks
If a malfunction occurs during operation, the "run lamp" and "inspection indicator" of the remote controller
blinks and the error code is displayed. Do a check and necessary procedures according to the content of
code.
The following display signal is shown simultaneously on the liquid crystal screen of the hour meter
("Operation time display") of the outdoor unit.
Refer to the table below and do the necessary checks and procedures.
If the unit does not operate, the hour meter does not display any error code, or operation halts
without any display, check the cause and perform the necessary procedures according to the service
manual.
To reset an error code, turn off the remote controller and press ENTER for more than 3 seconds on
the alarm display screen of the STOP mode on the PCB checker.
Outdoor unit
Run
display
Lamp
-
Blinking
-
Blinking
-
On
-
Blinking
-
Blinking
-
On
-
On
-
Blinking
-
On
-
On
-
Blinking
-
Blinking
-
Blinking
-
Blinking
-
Blinking
-
Blinking
-
Blinking
-
On
85
Item
:
GYEQ Models
Inspection
Unit
Remote control
display
No.
display
Blinking
Blinking
A0
Blinking
Blinking
A1
Off
Blinking
A1
Blinking
Blinking
A3
Blinking
Blinking
A6
Off
Blinking
A7
Blinking
Blinking
A7
Blinking
Blinking
A9
Off
Blinking
AF
Off
Blinking
AH
Blinking
Blinking
AJ
Blinking
Blinking
C1
Blinking
Blinking
C4
Blinking
Blinking
C5
Blinking
Blinking
C6
Blinking
Blinking
C9
Blinking
Blinking
CA
Off
Blinking
CE
NEXT . (2) Select the CH of the desired alarm/
NEXT , the code and operation time at occurrence
CH
13
1st most recent alarm
14
2nd most recent alarm
:
:
24
12th most recent alarm
Error
Indoor Unit - External Protection Device Failure
Indoor Unit - P Board Assembly Failure / EEPROM Misconfigured
Indoor Unit - P Board Assembly Failure
Indoor Unit - Drain Level System Failure
Indoor Unit - Fan Lock
Indoor Unit - Louver Motor (MA) Failure
Indoor Unit - Louver Motor Failure
Indoor Unit - Electronic Expansion Valve Drive Failure
Indoor Unit - Abnormal Drain
Indoor Unit - Dust Collector Failure
Indoor Unit - Capacity Setting Incorrect
Indoor Unit - Fan P Board / Adapter P Board - Control P Board
Transmission Failure
Indoor Unit - Fluid Pipe Thermistor Fault (contact failure, disconnected,
shorted, faulty)
Indoor Unit - Gas Pipe Thermistor Fault (contact failure, disconnected,
shorted, faulty)
Indoor Unit - Fan P Board - Control P Board Misconfigured
Indoor Unit - Inlet Air Thermistor Fault (contact failure, disconnected,
shorted, faulty)
Indoor Unit - Outlet Air Thermistor Fault (contact failure, disconnected,
shorted, faulty)
Indoor Unit/Person Detection/Floor Temperature Detection Sensor
Failure
– 18 –
SiAUY361411EA
Item
0FGHP-EN0841 DGJ002