6 Remote Monitoring
6-6
Checking (Reading) Setting
Parameters
Read the setting parameters using the Read Variable Area command.
The Read Variable Area command can read
single specified addresses one by one, but it can
also read multiple addresses together by
specifying an area. The latter case is convenient,
as the read operation can be completed with one
command/one response.
The area to specify is H'0020 to H'002F. Refer to 6-3 Variable Area Map on page 6-5.
The setting parameters can be read regardless of whether automatic measurement is being performed.
The reading operation does not affect the K7GE-MG operation.
6 - 12
Host system
Reading variable area
Read
H'0020 to H'002F
command
K7GE-MG
Insulation Resistance Monitoring Device User's Manual (N224)
Values of
H'0020 to
Response
H'002F