1.8   Rack Requirements
The OpenFlex Data24 is designed to be installed into a rack that meets the EIA-310 standard with a minimum
of 1000 mm (39.4 in.) of usable rack space, door to door. The vertical rack rails must be set between 700
mm – 850 mm / 28.26 in. – 33.46 in. to support the enclosure. It requires 2U of rack space, and it should be
installed into the rack at the lowest possible U height to keep the load on the rack balanced.
Table 11: Required Rack Specifications
Rack Depth
Rack Width
Rack Units (U)
Vertical Rack Rail Spacing
Static Load Rating
Dynamic Load Rating
Part Number
Parameter
Package Dimensions
W: 6.7 in x L: 11.6 in x H: 3 in
Requirement
1000 mm (39.4 in.) of usable rack space, door to
door
450mm (17.72in.) with 465mm (18.31in.) ± 1.5mm
nominal hole spacing. See EIA-310 Rack Standard
2U
700 mm – 850 mm / 28.26 in. – 33.46 in.
Rack meets ISTA 3E or 3B test requirements and
regulations when mounted to the shipping pallet
Rack meets ISTA 3E or 3B test requirements and
regulations when mounted to the shipping pallet