In some applications, depending on space and convenience re-
quirements, it may be desirable to install 2 filter driers and
sight glasses in a single circuit application. One filter drier and
sight glass may be installed at A locations (see Fig. 9) or 2 fil-
ter driers and sight glasses may be installed at B locations (see
Fig. 9 and 10).
Select the filter drier for maximum unit capacity and minimum
pressure drop. Complete the refrigerant piping from the indoor
unit to the outdoor unit before opening the liquid and suction
lines at the outdoor unit.
INSTALL LIQUID LINE SOLENOID VALVE
It is recommended that a solenoid valve be placed in the main
liquid line (see Fig. 9 and 10) between the condensing unit and
the evaporator coil. Locate the solenoid valve at the outlet end
of the liquid line, near the evaporator coil connections, with
flow direction arrow pointed at the evaporator coil. Refer to
Table 13. (A liquid line solenoid valve is required when the liq-
uid line length exceeds 75 ft [23 m].) This valve prevents re-
frigerant migration (which causes oil dilution) to the compres-
sor during the off cycle, at low outdoor ambient temperatures.
Wire the solenoid in parallel with the compressor contactor coil
(see Fig. 9 and 10). This means of electrical control is referred
to as solenoid drop control.
TXV
INDOOR
SENSING
COIL CKT
BULB
AIRFLOW
15 DIAMS
10
MIN
DIAMS
SINGLE CIRCUIT COIL PIPING CONFIGURATION
FOR SINGLE COMPRESSOR CONDENSING UNITS
TXV
INDOOR
SENSING
COIL CKT 2
BULB
AIRFLOW
15 DIAMS
10
MIN
DIAMS
8 DIAMS
TXV
SENSING
INDOOR
BULB
COIL CKT 1
AIRFLOW
15 DIAMS
10
MIN
DIAMS
DUAL CIRCUIT COIL PIPING CONFIGURATION
FOR SINGLE COMPRESSOR CONDENSING UNITS
Fig. 9 — Location of Sight Glass(es) and Filter Driers
Typical 569J***A/B/G/H Systems
EQUALIZER LINE
SIGHT GLASS
A LOCATION
FILTER DRIER
A LOCATION
TXV
8 DIAMS
MIN
LIQUID LINE
SOLENOID
VALVE
EQUALIZER LINE
SIGHT GLASS
A LOCATION
TXV
FILTER DRIER
CKT 2
A LOCATION
SIGHT
MIN
GLASSES
B LOCATION
FILTER
LIQUID LINE
DRIERS
SOLENOID
B LOCATION
VALVE
TXV
CKT 1
8 DIAMS
MIN
TXV
SENSING
BULB
AIRFLOW
15 DIAMS
10
MIN
DIAMS
TXV
SENSING
BULB
AIRFLOW
15 DIAMS
10
MIN
DIAMS
SUCTION
CIRCUIT 1
SUCTION
CIRCUIT 2
DUAL CIRCUIT COIL PIPING CONFIGURATION
FOR TWO CIRCUIT CONDENSING UNITS
Fig. 10 — Location of Sight Glasses and Filter Driers
Typical 569J***D/E/F Systems
Solenoid Drop Control Wiring
Control the power to the liquid line solenoid through a Sole-
noid Valve Relay (SVR) in all units. Use part number
HN61PC005 (field-supplied, installed). 569J***A/B/G/H unit
requires one SVR; 569J***D/E/F unit requires two relays.
A unit with two liquid line solenoid valves also requires a sep-
arate control power transformer for the liquid solenoid valve
loads. Select TRAN3 transformer part number according to
unit power supply.
QTY
RELAY SVR
MODEL
LSV
QTY - PART NUMBER
1
1 — HN61PC005
569J***
A/B/G/H
2
2 — HN61PC005
569J***D/E/F
2
2 — HN61PC005
569J*12F
2
1 — HN61PC005*
LEGEND
LSV
— Liquid Solenoid Valve
SVR
— Solenoid Valve Relay
N/R
— Not Required
N/R # — Not Required / Factory Installed
* Install as SVR-2 (SVR-1 is factory-installed).
Mount the SVR (and transformer TRAN3 when used) in unit
control box. Connect per wiring schematic label on unit.
NOTE: TRAN3 is provided with the HGBP factory installed op-
tion for 569J*12F units.
12
EQUALIZER LINE
TXV
CKT 2
8 DIAMS
MIN
SIGHT
GLASSES
LIQUID LINE
SOLENOID VALVE
FILTER
CIRCUIT 2
DRIERS
TXV
CKT 1
8 DIAMS
MIN
LIQUID LINE
SOLENOID VALVE
CIRCUIT 1
TRAN3 PRIMARY V:
PART NUMBER
N/R
208/230V: HT01BD202
460V: HT01BD702
575V: HT01BD902
N/R #