Remote Current Limit Reset Control - York YCIV Series Installation Operation & Maintenance

Air-cooled screw liquid chillers e/v high efficiency and s/p standard efficiency
Table of Contents

Advertisement

FORM 201.23-NM2
ISSUE DATE: 09/25/2020
Control Board jumper JP4 must be positioned correctly
to receive either a voltage (0 VDC through 10 VDC or
2 VDC through 10 VDC) or current (0 mA through 20
mA or 4 mA through 20 mA) signal. Place the jumper
in the "V" position for a voltage signal or mA for a cur-
rent signal (See Figure 27 on page 166 and Figure 28
on page 167). The software must be configured under
the OPTIONS key for the specific type of input signal
to be used.
The maximum temperature reset is achieved at either
10 VDC or 20 mA. Sending the minimum signal (0
VDC, 2 VDC, 0 mA, or 4 mA based on the OPTIONS
key setting) causes the setpoint to revert back to its lo-
cal programmed value. If the setpoint reset causes the
setpoint to go over the maximum programmable value,
it will be set to the maximum programmable setpoint.
0 VDC through 10 VDC Reset Input
A 0 VDC signal produces a 0°F reset. A 10 VDC signal
produces the maximum remote temp reset (program-
mable under the SETPOINTS key). The setpoint reset
is ramped linearly between these limits as the input
varies between 0 VDC and 10 VDC. In order for this
input to work properly, the Remote Temperature Reset
must be programmed for 0 VDC through 10 VDC in-
put (OPTIONS key) and Chiller Control Board jumper
JP4 placed in the "V" position.
2 VDC through 10 VDC Reset Input
A 0 VDC to 2 VDC signal produces a 0°F reset. A 10
VDC signal produces the maximum remote temp re-
set (programmable under the SETPOINTS key). The
setpoint reset is ramped linearly between these limits
as the input varies between 2 VDC and 10 VDC. In
order for this input to work properly, the Remote Tem-
perature Reset must be programmed for 2 through 10
VDC input (OPTIONS key) and Chiller Control Board
jumper JP4 placed in the "V" position.
0 mA through 20 mA Reset Input
A 0 mA signal produces a 0°F reset. A 20 mA signal
produces the maximum remote temp reset (program-
mable under the SETPOINTS key). The setpoint reset
is ramped linearly between these limits as the input
varies between 0 mA and 20 mA. In order for this in-
put to work properly, the Remote Temperature Reset
must be programmed for 0 mA through 20 mA input
(OPTIONS key) and Chiller Control Board jumper JP4
placed in the "mA" position.
JOHNSON CONTROLS
4 mA through 20 mA Reset Input
A 0 mA to 4 mA signal produces a 0°F reset. A 20 mA
signal produces the maximum remote temp reset (pro-
grammable under the SETPOINTS key). The setpoint
reset is ramped linearly between these limits as the in-
put varies between 4 mA and 20 mA. In order for this
input to work properly, the Remote Temperature Reset
must be programmed for 4 mA through 20 mA input
(OPTIONS key) and Chiller Control Board jumper JP4
placed in the "mA" position.
Local Current Limit Control
Local Current Limit Control is used to set the ac-
tual Current Limit Setpoint. This is accomplished by
changing the Local Current Limit Setpoint under the
PROGRAM key. This is the value at which the unit
will begin to current limit and override capacity control
if remote reset is not actively overriding this control. If
any other current limit methods are active, the lowest
value will be used.
Keep in mind that limiting current may interfere with
capacity control, pulling down chilled liquid tempera-
tures on hot water starts, and maintaining chilled liquid
setpoints.
Pulldown Current Limit Setpoint
The Pulldown Current Limit Setpoint can be set under
the PROGRAM key. This current limit setpoint is only
active on start-up for the time defined by the Pulldown
Current Limit Time under the PROGRAM key. After
the run time has exceeded this time, the Pulldown Cur-
rent Limit Setpoint is ignored.
This control is useful in limiting current pulldown de-
mand during peak usage periods where electric costs
are highest.
Keep in mind that limiting current may interfere with
capacity control, pulling down chilled liquid tempera-
tures on hot water starts, and maintaining chilled liquid
setpoints.

REMOTE CURRENT LIMIT RESET CONTROL

Remote Current Limit Reset is used to reset the actu-
al current limit setpoint used in current limit control.
There are several ways to change the current limit
setpoint. The first is by reprogramming the Local Cur-
rent Limit Setpoint under the PROGRAM key. This is
the value the unit will control the current limit to if
neither of the other methods is active.
SECTION 7 - OPERATION
215
7