Building Management System (Bms) - Bradford White eF Series Troubleshooting Manual And Instructions For Service

Ultra high efficiency water heater
Table of Contents

Advertisement

Building Management System (BMS)

All water heaters with ICON Systems can be equipped with a gateway kit that will facilitate a Building
Management System (BMS) connection to Modbus or Bacnet
factory installed. A full installation, operation, and troubleshooting manual is provided with the
gateway kit.
Before beginning any Troubleshooting operations listed below, please note that the gateway kit and BMS may
need to be disconnected from the heater. Please ensure this has been completed before proceeding with any
troubleshooting operation that may be impacted by settings in the BMS.
BMS Mapping
Map Descriptor
Name
Demand source
Firing rate
Fan speed
Flame signal
Tank temperature
sensor
Appliance setpoint
Burner status
Lockout code
Appliance status
DHW priority count
Burner run time
Controller cycle count
Controller run time
Alarm reason
DHW setpoint
12
Modbus
Read/Write
Register
00006
Read
00008
Read
00009
Read
00010
Read
00012
Read
00017
Read
00032
Read
00034
Read
00080
Read
00082
Read
00130/00131
Read
00142/00145
Read
00144/00145
Read
0035
Read
0453
Read/Write
®
. This kit is sold separately and is not
CAUTION
BACnet
Object ID
Current demand source:
0 = Unknown
1 = No source demand
2 = CH
3 = DHW
4 = Lead Lag slave
5 = Lead Lag master
001
6 = CH frost protection
7 = DHW frost protection
8 = No demand due to burner switch (register 199) turned off
9 = DHW storage
10 = Reserved
11 = Warm weather shutdown
12 = Hot standby
002
Actual firing rate (% or RPM)
003
RPM
004
0.01V or 0.01 μA precision (0.00-50.00V)
005
-40-130 (0.1C precision)
006
-40-130 (0.1C precision)
0 = Disabled
1 = Locked out
2-3 = Reserved
4 = Anti-short cycle
007
5 = Unconfigured safety data
6-33 = Reserved
34 = Standby Hold
35 = Standby Delay
0 = No lockout
008
1-4096
0 = Unknown
1 = Disabled
009
2 = Normal
3 = Suspended
Countdown of time when DHW has priority over CH (secs).
010
Applicable when DHW priority time is enabled.
011
Hours
012
0-999,999
013
Hours
0 = None
1 = Lockout
014
2 = Alert
3 = Other
015
40-130 (0.1C precision)
Note
12

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

60t12560t15060t199100t150100t199100t250 ... Show all