STARTUP AND CHECKOUT

After the installation is complete, check to be sure the system is working properly. See Table 4 for sequence of operation.
Table 4. Trol-A-Temp Electronic MiniZone Panel Sequence Of Operation.
LED
Device
INITIAL POWERUP
SYSTEM
Panel
(orange)
Damper
IDLE MODE
SYSTEM
Panel
(off)
PURGE MODE
ZONE
Thermostat None
(orange)
Damper
Panel
ZONE 1 INITIATES CALL FOR HEAT
SYSTEM
Thermostat W (heat)
(red)
Damper
Zone 1
(green).
Panel
ZONE 1 ENDS CALL FOR HEAT
SYSTEM
Thermostat None
(orange)
Damper
Panel
ZONE 1 INITIATES CALL FOR COOL
SYSTEM
Thermostat Y (cool)
(green).
Damper
Zone 1
(green).
Panel
ZONE 1 ENDS CALL FOR COOL
SYSTEM
Thermostat None
(orange)
Damper
Panel
Terminals
Energized
G (fan)
System enters Purge mode for 2-1/2 minutes.
Damper(s) open to all zones.
M4
None
No call for heating or cooling.
Damper from last zone to call remains open; all
others remain closed for 2-1/2 minutes after
M4
thermostat call ends.
G (fan)
After 2-1/2 minutes, if no other call for heating or
cooling is required, all dampers open.
Zone 1 thermostat calls for heat.
Zone 1 damper(s) remains open.
Zone1: M4
Zones 2 and 3 dampers close.
Zones 2 and
Panel calls for heat.
3: M6
W (heat)
System enters Purge mode.
Damper(s) from zone 1 remains open; all others
Zone 1: M4.
remain closed for 2-1/2 minutes after zone 1
Zones 2 and
thermostat call ends.
3: M6.
After 2-1/2 minutes, all dampers open (M4
G (fan)
energized).
Zone 1 thermostat calls for cool and fan.
G (fan)
Zone 1 damper(s) remains open.
Zones 2 and 3 dampers close.
Zone 1: M4.
Panel calls for cool and fan.
Zones 2 and
3: M6.
Y (cool).
G (fan).
System enters Purge mode.
Damper(s) from zone 1 remains open; all others
Zone 1: M4.
remain closed for 2-1/2 minutes after zone 1
Zones 2 and
thermostat call ends.
3: M6.
After 2-1/2 minutes, all dampers open (M4
G (fan)
energized).
EMM-3 ELECTRONIC MINIZONE™ PANEL
System Action
7
Comments
See Purge mode.
Equipment terminals are not
energized.
If SYSTEM LED flashes orange,
DATS is not connected or is out-
of-range.
Panel enters Purge mode after
each call for heat and cool; this
allows heat exchanger to
dissipate more conditioned air
into the zone.
Heat is delivered only in zone 1.
When another zone calls for heat
while zone 1 is calling, that zone
damper opens.
For electric heat applications, use
thermostat that calls for fan with
all calls for heat.
None.
Cool is delivered only to zone 1.
If another zone calls for cool while
zone 1 is calling, the damper to
that zone opens.
In retrofit applications, where only
three wires are available, Y
signal from thermostat activates
Y and G call from panel
None.
68-3041-2