C. Hearth Pad Requirements
EMBER PROTECTION: It is necessary to install a Type I
floor protector.
Floor protector must be non-combustible material,
extending beneath appliance with a minimum of 6 inches
(152mm) in front of glass and 6 inches (152mm) to both
sides of the fuel loading door. Open the door and measure
6 inches (152mm) from the side edge of the opening in the
face of the appliance.*See exception.
25-3/4 in.
minimum
Front of glass
6 in
6 in
from the fuel door
opening
USA
13-3/4 in.
Figure 13.1
Must extend 51mm
beyond each side
of pipe (shaded area)
to the wall thimble.
152mm
CANADA
Figure 13.2
March 17, 2020
(UL and ULC)
32-1/8 in.
minimum
6 in
652mm
minimum
Front of glass
152mm
152mm
from fuel door opening
348mm
USA INSTALLATIONS: A non-combustible floor protection
is recommended extending beneath the flue pipe when
installed with horizontal venting or under the Top Vent
Adapter with vertical installation.
CANADA INSTALLATIONS: A non-combustible floor
protection extending beneath the flue pipe is required
with horizontal venting or under the Top Vent Adapter with
vertical installation.
Fire Risk
Comply with all minimum clearances to
combustibles as specified.
Failure to comply may cause house fire.
37-1/2 in.
Figure 13.3
815mm
minimum
953mm
Figure 13.4
7074-803B
WARNING
46-1/4 in.
27-7/8 in.
13-3/4 in.
1173mm
Must extend 51mm
beyond each side
of pipe (shaded area)
to the wall thimble.
707mm
348mm
CANADA
USA
13