Replacing The Cpu Enclosure (Bottom) - Emerson FB2100 Field Replacement Manual

Flow computer cpu enclosure and electronics replacement
Hide thumbs Also See for FB2100:
Table of Contents

Advertisement

FB2100/FB2200 Flow Computer CPU Enclosure and Electronics Field Replacement Guide

Replacing the CPU Enclosure (Bottom)

1. Slide the connectivity board into the bottom of the new CPU enclosure. The
Ethernet port must fit into its matching opening on the side of the enclosure.
2. If present, replace the optional 6-channel expansion I/O board. See Replacing the
6-Channel Expansion I/O Board on page 18.
3. Replace the CPU board. See Replacing the CPU Board on page 16.
4. Reattach the adapter board. See Replacing the Adapter Board on page 14.
5. Reattach the CPU enclosure cover. See Replacing the CPU Enclosure Cover (Top) on
page 11.
6. Re-attach the CPU enclosure to the battery compartment. See Re-attaching the
CPU Enclosure to the Battery Compartment on page 9.
7. Re-connect the cable between the CPU enclosure and the sensor module.
8. Reattach the HMI module. See Replacing the HMI Module on page 7.