4.1 Technical data
Detector line
Line separator
A6V10227641_h_en_--
4 Specifications
Unless otherwise mentioned, the following data applies:
Temperature
Air pressure
You will find information on approvals on the data sheet for the device.
You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
●
Document A6V10271323
Operating voltage
Operating current
Maximum current connection factor
Quiescent current connection factor 6
Address connection factor
Separator connection factor
Protocol
Compatibility
Design
Line voltage:
●
Nominal
●
Minimum
●
Maximum
Voltage at which the line separator opens:
●
Minimum
●
Maximum
Permanent current when switches
are closed
Switching current (e.g., in the event
of a short-circuit)
Leakage current when switches are
open
Serial impedance when switches are
closed
= 25 °C
= 1000 hPa (750 Torr)
DC 12...33 V
Typ. 1 mA (0.6...25 mA)
16
2 + n*1 (n = number of radio devices)
1
FDnet/C-NET
See 'List of compatibility'
●
Inherently short-circuit-proof
●
Protected against polarity reversal
●
Protected against overvoltage
DC 32 V (= V
DC 12 V (= V
DC 33 V (= V
DC 7.5 V (= V
DC 10.5 V (= V
Max. 1.5 A (= I
Max. 2 A (= I
Max. 1 mA (= I
Max. 0.4 Ω (= Z
Specifications
Technical data
)
nom
)
min
)
max
)
SO min
)
SO max
)
C max
)
S max
)
L max
)
C max
15 | 20
4