368/368 FC/369/369 FC
Users Manual

Manual-Range Mode

To enable manual-range mode:
1.
With the Product off, simultaneously push  and .
2.
Hold both buttons until the backlight illuminates (~2 s).
The Product is now in manual-range mode.
3.
Push  to select the range.

Clean the Product

Periodically wipe the case with a damp cloth and mild detergent.
To avoid damaging the Product, do not use abrasives or solvents to clean the Product.
1.
Inspect the jaw mating surface for cleanliness. If any foreign material is present, the jaw will not
close properly and measurement errors will result.
2.
Open the jaws and clean the clamp metal ends with a lightly oiled cloth.