Start-Up; General; Pre Start-Up Checklist; Special Tools Required - Greenheck ERVe Series Installation, Operation And Maintenance Manual

Energy recovery ventilator
Hide thumbs Also See for ERVe Series:
Table of Contents

Advertisement

Start-Up

DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to OFF
at disconnect switch(es). Unit may have multiple
power supplies.
WARNING
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
Do not operate energy recovery ventilator without
the filters and birdscreens installed. They prevent the
entry of foreign objects such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to
internal components may result and void warranty.
General Start-Up Information
Every installation requires a comprehensive start-up
to ensure proper operation of the unit. As part of that
process, the following checklist must be completed and
information recorded. Starting up the unit in accordance
with this checklist will not only ensure proper operation,
but will also provide valuable information to personnel
performing future maintenance. Should an issue arise
which requires factory assistance, this completed
document will allow unit experts to provide quicker
resolve. Qualified personnel should perform start-up to
ensure safe and proper practices are followed.
Unit Model Number _______________________________
Unit Serial Number _______________________________
Energy Wheel Date Code ___________________________
Start-Up Date
_______________________________
Start-Up Personnel Name __________________________
Start-Up Company _______________________________
Phone Number
_______________________________
Pre Start-Up Checklist –
are completed.
Disconnect and lock-out all power switches
Remove any foreign objects that are located in the
energy recovery unit.
Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and
accessories for tightness.
®
(e.g. ERVe-20)
(e.g. 10111000)
(e.g. 0450)
check as items
Rotate the fan wheels and energy recovery
wheels by hand and ensure no parts are rubbing.
If rubbing occurs, refer to Start-Up section for
more information.
Check the fan belt drives for proper alignment
and tension. Refer to Start-Up section for
more information.
Filters can load up with dirt during building
construction. Replace any dirty pleated filters and
clean the aluminum mesh filters in the intake hood.
Refer to Routine Maintenance section.
Verify that non-motorized dampers open and
close properly.
Check the tightness of all factory
wiring connections.
Verify control wire gauge. Refer to the Electrical
Connections section.
Verify diameter seal settings on the energy
recovery wheel. Refer to Start-Up section for
more information.
Install exhaust inlet motorized damper. Refer to Unit
Accessories section.

SPECIAL TOOLS REQUIRED

• Voltage Meter (with wire probes)
• Amperage Meter
• Thermometer
• Tachometer
• Incline manometer or equivalent

Start-Up Checklist

The unit will be in operational mode during start-up. Use
necessary precautions to avoid injury. All data must be
collected while the unit is running. In order to measure
volts and amps, the control center door must be open,
and the unit energized using a crescent wrench to turn
the disconnect handle.
Check line voltage at unit disconnect
_______
L1-L2 volts
_______
L2-L3 volts
_______
L1-L3 volts
Motor Amp Draw
• Supply Fan
_______
L1 amps
_______
L2 amps
_______
L3 amps
• Energy Wheel
_______
L1 amps
_______
L2 amps
_______
L3 amps
Fan RPM
_______
Supply Fan
Correct fan rotation direction
Supply Fan
Exhaust Fan
• Exhaust Fan
______
L1 amps
______
L2 amps
______
L3 amps
______
Exhaust Fan
Yes / No
Yes / No
Energy Recovery Ventilator
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Erve-20Erve-35Erve-45Erve-55