Cooling Capacities - Models Dhe/Dhg048 - York D1HE/D1HG036 Technical Manual

Sunline ultra single package air-cooled air conditioners 3, 4 and 5 nominal ton 12.2 through 13.2 seer
Table of Contents

Advertisement

036-21216-003-A-0204
TABLE 7: COOLING CAPACITIES - MODELS DHE/DHG048
AIR ON
EVAPORATOR
COIL
TOTAL
1
CAP.
WB
MBH
CFM
°F
72
59
67
53
2000
62
47
57
47
72
58
67
53
1800
62
47
57
46
72
57
67
52
1600
62
46
57
45
72
54
67
49
1400
62
43
57
43
72
51
67
46
1200
62
41
57
40
AIR ON
EVAPORATOR
COIL
TOTAL
1
CAP.
WB
MBH
CFM
°F
72
50
67
45
2000
62
39
57
39
72
50
67
44
1800
62
39
57
38
72
49
67
44
1600
62
39
57
38
72
47
67
42
1400
62
37
57
36
72
44
67
40
1200
62
35
57
34
1.
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance
Table, multiply this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit
2.
These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan
motor power input is 0.36kW. Refer to Tables 10 and 11 for the kW of the supply air blower motor.
3.
These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from Tables 10 and 11, multiply
this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
NOMINAL RATING
Unitary Products Group
TEMPERATURE OF AIR ON CONDENSER COIL
85°F
SENSIBLE CAPACITY
POWER
ENTERING DRY BULB, °F
2
INPUT
86
83
80
77
3.3
46
40
34
28
3.2
53
49
43
38
3.2
47
47
47
42
3.1
47
47
47
41
3.3
42
37
32
27
3.2
50
46
41
35
3.2
47
47
46
41
3.1
46
46
46
41
3.3
39
34
30
25
3.2
47
42
38
33
3.2
46
46
45
41
3.1
45
45
45
40
3.2
35
31
27
23
3.1
43
39
35
31
3.1
43
43
42
38
3.1
43
43
41
37
3.2
32
29
25
22
3.1
39
35
32
28
3.1
41
41
38
35
3.0
40
40
38
34
TEMPERATURE OF AIR ON CONDENSER COIL
105°F
SENSIBLE CAPACITY
POWER
ENTERING DRY BULB, °F
2
INPUT
86
83
80
77
3.8
41
35
30
24
3.7
45
44
39
33
3.6
39
39
39
34
3.6
39
39
39
33
3.8
38
33
28
23
3.7
44
41
36
31
3.6
39
39
40
35
3.6
38
38
38
33
3.8
35
31
26
21
3.7
43
39
34
30
3.6
39
39
41
37
3.6
38
38
38
33
3.8
32
28
24
20
3.7
39
35
31
27
3.6
37
37
38
33
3.5
36
36
35
31
3.7
29
25
22
18
3.7
36
32
29
25
3.6
35
35
34
30
3.5
34
34
32
28
3
TOTAL
POWER
1
CAP.
INPUT
MBH
74
71
68
23
-
-
55
3.5
32
26
21
49
3.4
36
30
25
44
3.4
35
29
24
43
3.3
22
-
-
54
3.5
30
25
20
48
3.4
36
31
26
43
3.4
35
30
25
42
3.3
21
-
-
53
3.5
29
24
19
48
3.4
36
32
27
42
3.4
36
31
27
41
3.3
19
-
-
51
3.5
27
23
19
45
3.4
34
30
26
40
3.4
33
29
25
39
3.3
18
-
-
48
3.5
25
21
18
42
3.5
31
28
24
38
3.4
31
27
24
37
3.4
3
TOTAL
POWER
1
CAP.
INPUT
MBH
74
71
68
18
-
-
45
4.0
27
22
16
40
4.0
28
22
17
35
3.8
27
22
16
35
3.8
18
-
-
45
4.0
26
21
16
40
4.0
30
25
20
35
3.9
28
23
18
34
3.8
17
-
-
45
4.1
25
20
16
40
4.1
32
27
23
35
3.9
29
24
19
34
3.8
16
-
-
43
4.0
23
19
15
38
4.0
29
25
21
33
3.8
27
23
18
33
3.7
15
-
-
41
3.9
21
18
14
36
3.9
27
23
20
32
3.8
25
21
18
31
3.7
ALL SENSIBLE CAPACITY
95°F
3
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
2
86
83
80
77
74
43
37
32
26
20
49
47
41
35
30
44
44
44
38
32
43
43
43
37
31
40
35
30
25
20
47
44
39
33
28
43
43
43
38
33
42
42
42
37
32
37
33
28
23
19
45
41
36
32
27
42
42
43
39
34
41
41
41
37
32
34
30
26
22
17
41
37
33
29
25
40
40
40
36
32
39
39
38
34
30
30
27
23
20
16
37
34
30
27
23
38
38
36
33
29
37
37
35
31
28
115°F
3
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
2
86
83
80
77
74
39
33
28
22
16
40
40
37
31
25
35
35
35
30
24
35
35
35
29
23
36
31
26
21
16
40
39
34
29
24
35
35
37
32
27
34
34
34
29
24
33
29
24
20
15
40
37
32
27
23
35
35
39
34
30
34
34
34
30
25
30
26
22
18
14
37
34
29
25
21
33
33
35
31
27
33
33
31
27
23
27
24
20
17
13
34
30
27
23
20
32
32
32
28
25
31
31
29
25
22
71
-
24
26
26
-
23
28
27
-
22
30
28
-
21
28
26
-
20
26
24
71
-
20
18
18
-
19
22
19
-
18
25
20
-
17
23
19
-
16
21
18
9