Typical Field Control Wiring Diagram; Typical Field Power Wiring Diagram; Additional Static Pressure Resistance 3-1/2 - 5 Ton (Dnh042 - 060) - York AFFINITY 291627-YTG-B-0807 Technical Manual

Affinity series single package gas/electric air cooled air conditioners 2-1/2 through 5 nominal ton
Table of Contents

Advertisement

TABLE 14: ELECTRICAL DATA
LIMITATIONS
MODEL
POWER
DNH
SUPPLY
MIN.
030
208/230-3-60
187
030
460-3-60
414
036
208/230-3-60
187
036
460-3-60
414
042
208/230-3-60
187
042
460-3-60
414
048
208/230-3-60
187
048
460-3-60
414
060
208/230-3-60
187
060
460-3-60
414
1. Utilization range "A" in accordance with ARI Standard 110.
2. Dual element, time delay type.
18
VOLTAGE
COMPRESSOR
1
MAX.
RLA
LRA
253
8.6
55
504
4.3
27
253
11.4
77
504
5.7
39
253
13.9
88
504
6.4
44
253
13.0
93
504
6.4
46.5
253
19.3
123
504
10.0
62
SUPPLY
COND.
AIR
MINIMUM
FAN
BLOWER
CIRCUIT
MOTOR,
MOTOR
AMPACITY
FLA
FLA
1.1
2.6
14.5
0.6
1.4
7.4
1.1
3.5
18.9
0.6
1.8
9.5
1.3
3.5
22.2
0.7
1.8
10.5
1.9
4.2
22.4
1.0
2.1
11.1
1.9
9.4
32.9
1.0
4.7
16.0
291627-YTG-B-0807
MAX.
MAX.
HACR
UNIT
FUSE
BREAKER
POWER
SIZE,
SIZE,
FACTOR
2
AMPS
AMPS
20
20
.96
15
15
.96
25
25
.96
15
15
.96
30
30
.96
15
15
.96
30
30
.96
15
15
.96
45
45
.96
20
20
.96
Unitary Products Group
TRANSFORMER
SIZE (VA)
75
75
75
75
75
75
75
75
75
75