Expansion Tank - Trane Ascend ACS 140 Installation, Operation And Maintenance Manual

Air-cooled chiller
Table of Contents

Advertisement

I I n n s s t t a a l l l l a a t t i i o o n n - - M M e e c c h h a a n n i i c c a a l l

Expansion Tank

Water piping system shall be equipped with an
expansion tank, field installed outside of pump
package. Expansion tank should be capable of the
Table 13. Expansion tank volume selection examples (diaphragm tank type)
Example
Description
Maximum Pressure
Acceptance Expansion Tanks Volume Req.
1
Acceptance volume
Tank Volume Required
Maximum Pressure
Acceptance Expansion Tanks Volume Req.
2
Acceptance volume
Tank Volume Required
Maximum Pressure
Acceptance Expansion Tanks Volume Req.
3
Acceptance volume
Tank Volume Required
Maximum Pressure
Acceptance Expansion Tanks Volume Req.
4
Acceptance volume
Tank Volume Required
34
thermal expansion of a loop volume equivalent to three
(3) minute loop at rated flow. See volume calculation
methods in ASHRAE-Handbook-Equip. 2012, section
13.5.
Units
140
160
psi
30
30
gal
26
29
gal
28
36
gal
33
37
psi
45
45
gal
22
25
gal
28
28
gal
28
32
psi
125
125
gal
17
20
gal
20
20
gal
22
25
psi
150
150
gal
17
19
gal
20
20
gal
21
24
Unit Size (tons)
180
200
215
30
30
30
33
37
40
36
49
49
42
46
50
45
45
45
28
31
33
36
36
36
35
39
42
125
125
125
22
24
26
28
28
36
28
31
33
150
150
150
21
24
26
28
28
28
27
30
33
AC-SVX002D-EN
230
30
42
49
53
45
36
36
45
125
28
36
36
150
27
28
35