Trane GVAF Series Installation Operation & Maintenance page 45

R134a-r1234ze-r513a air cooled high speed centrifugal chiller
Table of Contents

Advertisement

4. Turn power on by closing the unit supply-power fused-
disconnect switch.
5. Read the phase sequence on the indicator. The ABC LED
of the phase indicator will glow.
Sound power levels
CAUTION! Humidity : Do not leave compressor
uncovered
Discharge
If the compressor is installed in a humid environment, drip
trays may be required to collect condensate. Insulation
Measurement conditions:
should be installed on the suction valve/piping and the end
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
cap as this is where condensation is most likely to form.
long) fixed to its discharge opening.
It is recommended to fit an end cap insulator in a humid
environment.
Fan
Unit
speed
In humid environments, the bell housing of the compressor
1
should be insulated. A bell housing cover thermal insulator
FWD 08
2
3
is available as a compressor accessory.
1
FWD 10
2
WARNING! It is imperative that L1, L2, and L3 in the starter
3
be connected in the A-BC phase sequence to prevent
1
equipment damage due to reverse rotation.
FWD 12
2
3
WARNING!To prevent injury or death due to electrocution,
1
take extreme care when performing service procedures with
FWD 14
2
electrical power energized.
3
1
CAUTION! Do not interchange any load leads that are from
FWD 20
2
the unit contactors or the motor terminals. Doing so may
3
damage the equipment.
Intake
Water System Flow Rates
Measurement conditions:
Measurements taken at the horizontal air intake.
Establish a balanced chilled-water flow through the
evaporator. The flow rates should be between the
Fan
minimum and maximum values given on the pressure
Unit
speed
drop curves.
1
FWD 08
2
3
1
FWD 10
2
3
1
FWD 12
2
3
1
FWD 14
2
3
1
FWD 20
2
3
CTV-SVX009D-GB
UNT-PRC002-GB
Power level in dB(A), per Hz frequency band
125
250
500
55
50
42
57
54
47
58
57
50
57
51
45
58
54
48
60
58
50
57
51
45
58
54
48
60
58
50
56
62
50
61
66
55
63
69
58
57
63
51
61
66
55
63
69
58
Power level in dB(A), per Hz frequency band
125
250
500
56
55
55
63
62
60
66
65
63
62
58
55
66
63
60
70
67
63
62
58
55
66
63
60
70
67
63
66
65
65
73
72
69
78
76
73
68
72
64
76
76
68
78
79
71
Water System Pressure Drop
Measure the water-pressure drop through the evaporator
on the field installed pressure taps on the system water
piping. Use the same gauge for each measurement. Do
not include valves, strainers, or fittings in the pressure
drop readings.
Integrated Pump Package (Optional)
Before starting up the pump, the pipe system must be
thoroughly cleaned, flushed and filled with clean water.
Do not start the pump until it has been vented. To ensure
correct venting, open the vent screw located on the
pump housing on the suction side (see next figure).
1000
2000
37
37
40
30
CAUTION! When using freeze inhibitor, never fill the
42
32
system with pure glycol; this will damage the shaft seal.
42
34
Always fill the system with diluted solution. Maximum
45
38
concentration of glycol is 45% for unit with pump
48
40
42
34
package.
45
38
48
40
48
39
If the chiller is installed in a humid environment or a
53
47
location with high air humidity, the bottom drain hole
56
50
on the pump motor should be opened. The enclosure
49
40
class of the motor is then changed from IP55 to IP44. The
53
47
function of the drain holes is to drain off water which has
56
50
entered the stator housing with air humidity.
Figure 22 – Pump Package
B
B
F
1000
2000
53
46
60
53
62
56
58
51
62
56
65
59
58
51
62
56
C
65
59
65
57
C
71
64
75
69
64
56
71
65
A = Pump vent screw
74
69
D= Drain and fill valve
B = Air vent valve
= Pump drain plug
C = Drain valve
= Motor drain hole plug
Pre-Start Checkout
Overall power
4000
8000
dB(A)
31
30
46
38
40
50
40
43
53
33
28
48
39
35
51
42
39
54
33
28
48
39
35
51
42
39
54
38
36
56
46
45
60
50
49
63
39
37
57
46
45
60
50
49
63
F
A
Overall power
A
4000
8000
dB(A)
45
42
57
53
53
64
55
57
67
48
44
61
55
52
66
59
57
69
48
44
61
55
52
66
59
57
69
50
46
68
59
57
74
E
E
D
64
63
78
52
50
69
61
61
75
66
66
78
E
F
11
45

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents