Download Print this page

Care And Maintenance - Johnson Controls Tyco DV-5a Series Manual

Automatic water control valve
Hide thumbs Also See for Tyco DV-5a Series:

Advertisement

Care and
Maintenance
The following procedures and inspec-
tions must be performed as indicated,
in addition to any specific require-
ments of the NFPA and any applicable
standards recognized by the Approval
agency. Any impairment must be imme-
diately corrected. Refer to Figure 16, 17,
or 18, as applicable.
NOTICE
The frequency at which the following
procedures and inspections are to be
performed are to be in accordance with
the NFPA and any applicable specific
requirements of the standards recog-
nized by the Approval agency.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection systems
must first be obtained from the proper
authorities and all personnel who may
be affected by this action must be
notified.
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this docu-
ment, as well as with the NFPA and any
applicable standards recognized by the
Approval agency. Contact the install-
ing contractor or product manufacturer
with any questions.
Some procedures in this section result
in the operation of the associated
alarms. Notify the owner and the fire
department, central station, or other
signal station to which the alarms are
connected before performing the tests.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with the
NFPA and any applicable standards
recognized by the Approval agency.
Drop in Water Supply Pressure
Below Normal Range
NOTICE
If the water supply pressure is signif-
icantly reduced below the normally
expected static pressure range (as
could occur in the case of a water main
break or repair), and there is a subse-
quent drop in the diaphragm chamber
water pressure below its normal range
(for example, due to a leak in a piping
connection to or from the diaphragm
chamber or, a leak in the diaphragm
chamber check valve caused by dirt or
debris in the check valve seal area), a
deluge valve such as the DV-5
inadvertently trip, if its water supply
pressure is quickly restored.
A drop in the water supply pressure
to below its normal range (as in the
case of an interrupted water supply
condition) constitutes an emergency
impairment.
Should this condition occur, immedi-
ately close the System Main Control
Valve (B) and use the following proce-
dure to reset the system:
Step 1. Prior to the water supply pres-
sure being restored to the closed
System Main Control Valve (B), note the
pressure indicated by the Diaphragm
Gauge (K) and determine if the pres-
sure is within the normally expected
range.
Step 2. If the diaphragm chamber pres-
sure is below the normal range, check
for and correct any source of leakage
from the diaphragm chamber prior to
resetting the system.
Step 3. After the water supply pres-
sure is restored to the System Main
Control Valve (B), reset the DV-5
in accordance with the Valve Setting
Procedure section.
NOTICE
For fire protection systems subject to
an emergency impairment caused by
an interrupted water supply condition,
it is recommended that consideration
be given to installing a low water supply
pressure switch with the appropriate
alarm/indications to monitor the water
supply pressure.
Waterflow Alarm Test Procedure
To test the waterflow alarm, open the
Alarm Test Valve (G), which will allow a
flow of water to the Waterflow Pressure
Switch (C) and/or Water Motor Alarm.
Upon satisfactory completion of the
test, close the Alarm Test Valve (G).
To ensure drainage of the alarm line,
depress the plunger on the Automatic
Drain Valve (F).
Supervisory Low Pressure Alarm
Test Procedure
Proper operation of the Supervisory
Low Pressure Switch (T) must be per-
formed as follows:
Step 1. Open the System Drain Valve
(E) just enough to slowly relieve super-
visory air pressure from the system.
Verify that the Supervisory Low Pres-
sure Switch (T) is operational and that
the low pressure set point is approxi-
mately 5 psi (0,34 bar).
Step 2. Close the System Drain Valve
(E) and allow the system supervisory
pressure of 10 ± 2 psi (0,69 ± 0,14 bar)
to be automatically re-established. The
could
a
Supervisory Low Pressure Switch (T)
should return to its normal condition.
Pressure Relief Valve Maintenance
Over pressurization of the system
piping with air will result in the opening
of the Supervisory Air Pressure Relief
Valve (S). If the Supervisory Air Pres-
sure Relief Valve (S) continues to bleed
air after the system pressure has been
reduced to its normal supervisory pres-
sure range of 10 ± 2 psi (0,69 ± 0,14
bar), most likely debris became lodged
in the seating area. To help clean the
seating area, slowly pull up on the ring
at the top of the Supervisory Air Pres-
sure Relief Valve (S) to allow a full flow
of air through the Supervisory Air Pres-
sure Relief Valve (S), and then release
the ring to allow the Supervisory
Air Pressure Relief Valve (S) to snap
closed. Repeat the cleaning procedure
as necessary.
Wet Pilot Actuation
Operation Test Procedure
Proper operation of the DV-5
(i.e., opening of the DV-5
during a fire condition) must be veri-
Valve
a
fied as follows:
Step 1. If water must be prevented
from flowing beyond the riser, perform
the following steps:
• Close System Main Control Valve (B).
Open Main Drain Valve (D).
• Open System Main Control Valve (B)
one turn beyond position at which
water just begins to flow from Main
Drain Valve (D).
• Slowly close the Main Drain Valve (D).
Step 2. Open the Inspector's Test
Connection.
Note: Be prepared to quickly perform
Steps 3, 4, and 5 if water must be pre-
vented from flowing beyond the riser.
Step 3. Verify that the DV-5
tripped, as indicated by the flow of
water into the system.
Step 4. Close the System Main Control
Valve (B).
Step 5. Close the Diaphragm Supply
Valve (P).
Step 6. Reset the DV-5
dance with the Valve Setting Procedure.
Dry Pilot Actuation
Operation Test Procedure
Proper operation of the DV-5
(i.e., opening of the DV-5
during a fire condition) must be veri-
fied as follows:
Step 1. If water must be prevented
from flowing beyond the riser, perform
the following steps:
• Close System Main Control Valve (B).
Open Main Drain Valve (D).
TFP1425
Page 27 of 34
Valve
a
Valve as
a
Valve has
a
Valve in accor-
a
Valve
a
Valve as
a

Advertisement

loading