Bay control REC670
Version 2.2
Table 61. Phase voltage differential based capacitor bank unbalanced protection SCPDPTOV
Parameters
Phase voltage differential level
Reset Ratio
Minimum Bus Voltage
Independent time delay at 0 to 2 x Uset
Reset time Delay at to 2 x Uset to 0
Inverse time characteristics
Minimum Operate Time for Inverse Curve
Operate Time, START at 0 to 2 x Uset
Reset Time, START at 2 x Uset to 0
Critical impulse time
Impulse margin time
Table 62. Voltage unbalance protection of shunt capacitor bank SCUVPTOV
Function
Neutral voltage unbalance level
Reset ratio
Minimum bus voltage
Independent time delay at 0 to 2 x U
Reset time delay at to 2 x U
Inverse time characteristics
Minimum operate time for inverse curve
Operate time, START at 0 to 2 x U
Reset time, START at 2 x U
Critical impulse time
Impulse margin time
Hitachi Power Grids
GUID-42E90A81-B44D-42C1-B9B5-CD4CDB6E376C v1
Range
(1.0-95.0) % of UBase
>90 % at (5.0 – 95.0)% of UBase
>45% at (1.0 – 5.0)% of UBase
(5.0-100.0) % of UBase
(0.00-60.00) s
(0.00-60.00) s
Programmable
(0.00-60.00) s
Min = 30 ms
Max = 60 ms
Min = 15 ms
Max = 35 ms
20 ms typically at 0 to 2 x Uset
20 ms typically
GUID-47B33B7C-0F5E-4731-A7A8-FF1BDA5D5F41 v1
Range
(1.0-95.0) % of UBase
>90% at (5.0 – 95.0)% of UBase
>45% at (1.0 – 5.0)% of UBase
(5.0 - 100.0)% of UBase
(0.00-60.00) s
set
to 0
(0.00-60.00) s
set
Programmable
(0.00-60.00) s
Min = 30 ms
set
Max = 60 ms
to 0
Min = 15 ms
set
Max = 35 ms
20 ms typically at 0 to 2 x U
20 ms typically
© Copyright 2017 Hitachi Power Grids. All rights reserved
Accuracy
±0.5% of Ur
-
±0.5% of Ur
±0.2% or ±70 ms whichever is greater
±0.2% or ±45 ms whichever is greater
±5.0% or ±70 ms whichever is greater
±0.2% or ±70 ms whichever is greater
-
-
-
-
Accuracy
±0.5% of Ur
-
±0.5% of Ur
±0.2% or ±65 ms, whichever is greater
±0.2% or ±45 ms, whichever is greater
±5.0% or ±65 ms, whichever is greater
±0.2% or ±65 ms, whichever is greater
-
-
-
set
-
1MRK 511 404-BEN N
87