Table 8 Electrical Specifications - Bard 11EER WA Series Installation Instructions Manual

Wall mount air conditioner
Table of Contents

Advertisement

Rated Volts &
MODEL
Phase
W12AB-A0Z
A03
230/208-1
A05
W12AB-K00
115-1
K02
W12AB-D0Z
240/220-1
D03
 Maximum size of the time delay fuse or circuit breaker for protection of field wiring conductors.
 Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electrical code
(latest version), Article 310 for power conductor sizing.
CAUTION: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special
attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three current carrying
conductors are in a raceway.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and
conductor wires in accordance with the National Electrical Code and all local codes.
TABLE 8
Electrical Specifications
No. Field Power
Circuits
Minimum Circuit
Ampacity
1
9
1
20
1
28
1
17
1
28
1
9
1
20
Single Circuit
Maximum External
Field Power
Fuse or Ckt. Brkr.
Wire Size
15
14
20
12
30
10
30
10
30
10
15
14
20
12
Ground Wire
14
12
10
10
10
14
12
Manual 2100-715B
Page
23 of 25