4 Installation and Commissioning
4.4

HMI project part

Expanding the "Overview" display

4.4.1
In the "Fan view" display, the data of the fan to be displayed are copied to the
Register".fan[0] placeholder by selecting the respective fan. In doing so, you can
visualize the data of each fan.
The "Overview" display shows the input registers of several fans side by side. The
following chapter shows how to expand the overview screen.
Table 4-7
No.
1.
Open the HMI tags of the KTP900
operator panel.
Copy a "Fan_x" tag table and paste
it.
A new tag table with the next available
number is created (here: "Fan_5").
2.
Open the new tag table "Fan_5".
The column "PLC tag" still contains the
copied reference to "fan[4]".
Select all entries and confirm "Ctrl" +
"F".
Controlling several fans (ebm-papst) via Modbus RTU
Entry ID: 109476801,
V2.0,
Action
09/2018
Remarks
31