Pos.
Component
1
Inscription strips
Type of line
Control lines
'Sector valve'
'Main valve'
Control lines
'Alarm horn'
'Illuminated warning panel'
Detection lines
'Manual activation'
'Stop/blocking button'
Detection lines
'Loss of extinguishing agent'
'Extinguishing blocked'
Detection line
'Extinguishing activated'
Control console for B3Q440
serial interface
* reversed polarity in 'active' status
** with mains operating 29V
Fire & Security Products
Siemens Building Technologies Group
3.5
Control terminal AlgoPilot B3Q460/48x,
B3Q660/68x
Preparation
insert
B3Q460/48x
4

Calibration on E3G080

Each output and each input is controlled and set accordingly. In doing so, the relays for the valve
actuation are blocked by both the hardware and software; the valves can no longer be activated.
The illuminated warning panel and the horn are blocked by the software only.
Before initiating the automatic calibration, the tension at the terminals must be checked. All swit-
ches must be in "Rest" position (see the following table).
4.1
Line voltages E3G080
Line voltage
Terminals
'quiescent'
X10-..
(line termination with 4k75)
1/2
without R60/61
2/3
with R60/61
4/5
2.3V ± 10%
6/7
8/9
22.3V ± 10%
9/10
12/13
2.3V ± 10%
14/15
16/17
19,6V **
18/19
Details see document 1260
Ü
B3Q660/68x
B3Q660/680
1
from index y'AB' (Type FM)
Monitor-
ing
current
î 80..800mV
î 0.3...1.6V
5mA
0.5mA
4.7mA
0.5mA
resistor
2k25
Voltage cannot be measured with a voltmeter
Default
−> delivered with strips in 'english' for
AlgoPilot B3Q460/48x, B3Q660/68x, or
to be created with Word template (docu-
ment 006516)
Line
Line
voltage
voltage
'short
'open line'
circuit'
≥880mV
≤100mV
≥1.75V
≤200mV
≥3.5V
≤350mV
≥25V
≤2.6V
≥3.5V
≤350mV
≤2.7V **
≥22V
Line
voltage
'active'
Section
24...30V
24...30V *
3...12V
400mV..1.3V
3...14V **
9