Pos.
Component
1
Distributor cable: Line links of the extinguis-
hing sections
2
Flat cable F12A100/F12A470: Connection to
line module connector 'ST10'
3
Connection level
2
Pos.
Component
1
Inscription strips
2
Programming switch 'S3': Equipment ad-
dress
3
Programming switch 'S2': Key click, Buzzer
4
Resistor 'R2': Line termination for the com-
munication to E3G080
5
EPROM 'D1'
6
Plug-in terminals 'ST1' / 'ST2'
8
Fire & Security Products
Siemens Building Technologies Group
3.3
Emergency operation link E3G110
Preparation
to connect and to shunt according to system documenta-
tion
connect according to system documentation
. Details see also description in document 1260
check that all peripheral equipment planned is connected
(according to the system documentation)
ST10
ST1
3.4
Operating unit 'Extinguishing' B3Q440
Preparation
insert
set according to system documentation
set according to system documentation
'S2-1' −> 'ON' = Key click active
'S2-2' −> 'ON' = Buzzer active
set according to system documentation, is not the last
device, remove resistor 'R2', see description in document
1260 −> E3G080
check version, see Release notes docu 004767
connect according to system documentation
3
2
S3
4
R2
2
ST12
ST11
1
S2
5
ST2
6
ST1
Default
not inserted (contained in module)
order separately
−
3
Default
not insert
−> delivered with strips in 'english'
for operating unit 'extinguishing
B3Q440 and AlgoPilot, or to be
created with Word template DOT
(document 006516)
Address 1 ('OFF')
set to 'OFF'
inserted
inserted
supplied with B3Q440
1
005109_b_en−2
07.2004