Maximum Number Of I-Bus-Modules; Limits Of 5V Supply; Control Terminal Limits (Fc/Ft); Limitation Of Visible Texts On A Fc700A - Siemens FC700A System Planning Manual

Fire detection system
Table of Contents

Advertisement

8.1.5

Maximum number of I-Bus-modules

8.1.6

Limits of 5V supply

8.2

Control terminal limits (FC/FT)

8.2.1

Limitation of visible texts on a FC700A

8.2.2

Limitation of visible texts on a FT700A

Siemens Building Technologies
Fire & Security Products
Table 'Maximum number of I-Bus-modules'
Station type
I-Bus modules
1) Limited by software
2) Value based on experience (depends on cabinet size and/or 5V current consumption)
3) Battery charging unit E3C011 counts as one I-Bus module
All I-Bus modules are supplied with 24V and 5V. The available current for the 5V,
supplied from main CPU is limited:
'Main CPU'
B3Q700 / E3C011
Table '5V-Current consumption of I-Bus modules'
Current consumption
I-Bus module
E3M080
E3M111
E3L020
E3L030
E3G050
* Not an I-Bus module, but supplied via the 'Main CPU'
The number of texts of other stations (i.e. AREAS) that can be displayed on one
control terminal is limited by 14'000 texts.
To evaluate how many control panels FC700A can be displayed to one FC700A,
the following calculation must be used:
Twice the number of visible sections (worst case 1000)
+ The number of visible ZONES (worst case 1000)
+ The number of visible ELEMENTS with element text (worst case 1000)
= Number of texts per FC/FT (worst case 4000)
Example (worst case)
14'000 : 4000 (e.g.) = 3 fully configured FC can be displayed to one FC
The number of texts of other stations (FC700A) that can be displayed on one con-
trol terminal is limited by 14'000 texts.
To evaluate how many control panels FC700A can be displayed to one FT700A,
the following calculation must be used:
Twice the number of visible sections (worst case 1000)
+ The number of visible ZONES (worst case 1000)
+ The number of visible ELEMENTS with element text (worst case 1000)
= Number of texts per FC/FT (worst case 4000)
Example (worst case)
30'000 : 4000 (e.g.) = 7 fully configured FC can be displayed to one FT
FC700A
... 16
I-Bus module
from 'Main CPU'
55mA
25mA
10mA
35mA
8mA
Limitations of C-Bus participants
1)
... 8
2) 3)
Available current
250mA
Current consumption
from 'Main CPU'
E3G060
10mA
E3G070
10mA
E3C011
12mA
E3I020*
100mA
E3I040
70mA
007836_a_en_--.doc
21