3–24
"B" Group: Fine Tuning Functions
Software Lock Mode
The software lock function keeps personnel from accidentally changing parameters in
the inverter memory. The feature has some options, but the software lock function (B21)
is not protected from operator editing. You can lock all other parameters except the
output frequency (F01), if desired. This allows the user to vary only the output
frequency.
NOTE: Since the software lock function B31 is always accessible, this feature is not the
same as password protection used in other industrial control devices.
Func.
Name
Code
B31
Software lock mode
selection
NOTE: If redundant data protection is necessary, use one of the intelligent input
terminals (1 to 5) to allow a data change only when SFT is Off.
"B" Function
Description
Prevents parameter changes, in
four options, option codes:
00 ...all parameters except B31
are locked when SFT from
terminal is on
01 ...all parameters except B31
and output frequency F01
when SFT from terminal is on
02 ...all parameters except B31
are locked
03 ...all parameters except B31
and output frequency F01
setting are locked
Defaults
DOP,DRW,DOP+
Run-
time
EU/
Func.
Units
Edit
US
Code
01
F25
Name
S-LOCK