For cooling purposes, be sure that the inverter is installed veftically ln addition'
be sure that
it i. iip-ui"i
iio- oiher components and walls' lf foreign matter is introduced
into the
interio; of the inverter, this mty cause malfunctions, so male sure thal no
torelgn matter carl
entef l[.
NOTE: Install rhc invencr venicallv.
Do not install it on the floor or horizonlally'
NOTE l: The inverter should be installed in a locked enclosure that
meets tho requrrements
in lP4X (see EN60529).
NOTE 2: When an inverter (055HF to l50HD is installed outside lul
enclosure' the top ol
the inverter needs to be covered with the optional blind cover'
The hisher the ambient temperature inside the inverter' the shorter its
life will be'
iir tt"i n"n..utins unll is used near lhe invener' try lo krep il a\ lar^awal
as
.
possible.'Also.
wh'en inslalling lhe inverter in a bo\' be sure to carelully con, loer
ventilation and the dimenstons
For EMC direcrive and Low Voltage directive, do not remove the front cover'
The end application must be in accordance with BS EN6020'l- 1'
Each of irwerters 220HF to I IOOHF must be installed in a locked enclosure'
NOTE 3:
NOTE 4:
NOTE 5:
NOTE 6:
+
I\
CAUTION
Be sure lhat the wall surface is a nonflammable
material, such as steel Plate.
A Be "ure to check the ambient temperalure
Applicable model
Pla!e (,f installttion
055 to 1l00HF
(NOTE 6)
- l0 to 50'C
within the enclosurc
(NOTE l)
-10 to 40'C
055 ro l50HF
-10 to 40'C
Outside the enclosure
(NOTE 2)
-10 to 40'C