Required Number Of Outlets/Sockets; Circuit Protectors; Table 16 Required Conditions For Distribution Board Circuit Protectors - Fujitsu ETERNUS DX8100 S3 Site Planning Manual

Hybrid
Hide thumbs Also See for ETERNUS DX8100 S3:
Table of Contents

Advertisement

1.
ETERNUS DX Installation
Outlet/Socket Specifications

Required Number of Outlets/Sockets

The number of power outlets/sockets required to install the ETERNUS DX depends on the number of enclosures
and power distribution units.
It is recommended that the power cords of the enclosures are connected to the power distribution units that are
installed in the same rack. Secure the necessary number of power outlets within the same rack to avoid connect-
ing power cords to power outlets in different racks. It may be necessary to purchase additional power distribu-
tion units depending on the installation locations of enclosures.
Without Power Distribution Units
Four power sockets are required for each frontend enclosure.
Two power sockets are required for every controller enclosure, 2.5" type drive enclosure, and 3.5" type drive en-
closure.
With Power Distribution Units
Two power sockets are required for each power distribution unit.

Circuit Protectors

Protection coordination must be secured between the distribution board circuit protectors and the ETERNUS DX
or power distribution units to protect the ETERNUS DX by blocking the failed circuit immediately when a power
supply input error occurs.
Distribution board circuit protectors must satisfy the following required conditions and breaking characteristics.
Required Conditions
The distribution board circuit protectors must satisfy the required conditions that are listed below.

Table 16 Required Conditions for Distribution Board Circuit Protectors

Connected device
Power distribution unit (AC200-240V, horizontal type)
Power distribution unit (AC200-240V, vertical type)
ETERNUS DX (without power distribution units)
FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide
Power supply voltage
AC 200 – 240V
AC 200 – 240V
AC 100 – 120V
AC 200 – 240V
43
Copyright 2020 FUJITSU LIMITED
Current capacity
Regions other than
The EMEIA, Central
the EMEIA, Central
American, and Car-
American, and Car-
ibbean regions
ibbean regions
30A
30A
15A
16A
P3AM-9422-13ENZ0

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eternus dx8700 s3Eternus dx8900 s3

Table of Contents