Programmable Controller (40Vm900003) - Carrier 40VMI Series Installation And Maintenance Instructions Manual

1-way cassette indoor unit for variable refrigerant flow (vrf) systems
Table of Contents

Advertisement

Programmable Controller (40VM900003)

When setting an address, connect only one wired controller to
an indoor unit.
1. Press FAN and BACK simultaneously for five seconds to
access parameter settings as shown in Fig. 40.
MODE
MENU
FAN
TEMP. DOWN
Fig. 40 —Programmable Controller
IDU Addressing Menu
2. Press TEMP. UP or TEMP. DOWN to move the cursor
and choose IDU ADDRESSING. Press MENU/OK to
access this setting.
TEMP. UP
ON/OFF
OK
BACK
(40VM900003)
3. Press TEMP. UP or TEMP. DOWN to choose the
address you want to set. See Fig. 41. Press MENU/OK to
send this address to the IDU.
MODE
FAN
Fig. 41 —Programmable Controller
4. Press BACK twice or wait 30 seconds to automatically
exit the parameter settings menu.
19
TEMP. UP
MENU
OK
TEMP. DOWN
(40VM900003)
Setting IDU Address
ON/OFF
BACK