Step 3 - Mount The Unit - Carrier 40VMI Series Installation And Maintenance Instructions Manual

1-way cassette indoor unit for variable refrigerant flow (vrf) systems
Table of Contents

Advertisement

Ceiling
Angular Range for Airflow
NOTE: Dimensions are in inches.
Fig. 5 —Distance from Wall of Obstruction
• Do not position the unit where the discharge air could
blow directly on the thermostat.
• Recommended distance between 2 units is 10 feet to
avoid conflicting airflow and recirculation.
• The unit should not be positioned directly above any
obstruction.
• The unit must be installed square and level.
• Condensate drain should have sufficient downward slope
(1 inch per 100 inches) in any horizontal run between
unit and drain. Maximum condensate lift is 27-
IMPORTANT: Be sure that the ceiling grid is supported
separately from the unit. The ceiling grid must not be
supported by any part of the unit or any associated
wiring or piping work.
In case of new construction once the unit is installed, cover the
fan motor opening using the construction cover board to avoid
any dust and debris from settling inside the unit. Use the M4
bolt, washer, and nut as shown in Figs. 6 and 7 below.
Fig. 6 —Installation Paper
Return
Air Inlet
Floor
/
inches.
1
2
Screws for panel installation: M4X22 (6)
Fig. 7 —Secure Plate
Remove all buffers between the fan and the flared mouth
before installing the indoor unit. Failure to do so will cause
damage to the fan motor.
Ensure the unit is placed horizontally to avoid equipment
damage.
Step 3 — Mount the Unit —
INSTALLING HANGER BOLTS — Install the hanger bolts
at the locations shown in Fig. 8. Use 3/8-inch all-threaded rod.
For unit weight, see Table 1.
SIZE
LETTER
A
B
C
D
Fig. 8 —Installing Hanger Bolts
NOTE: Dimensions are in inches.
MOUNTING UNIT — The unit can now be lifted on to the
hanging rods for mounting.
1. Use rods and fasteners to suspend the unit at the factory-
provided mounting holes.
2. Adjust the height of the unit until the bottom (without
grille) is level with the false ceiling.
3. Secure the unit in position with locknuts and washers on
both sides of the unit bracket. Ensure that the threaded
rod does not protrude more than 2 inches below the
mounting brackets as shown in Fig. 9.
8
CAUTION
CAUTION
Bolt positioning dimension: D
Size of opening in ceiling: C
5-12
15-24
16-7/8
18-1/2
11-3/8
11-3/4
43-1/4
50-3/4
40
48-5/8