Wireless Remote Controller (40VM900001)

(included with the outdoor unit) —
dressing can be performed using the wireless remote controller.
When using the wireless controller, the user must maintain a
line of sight with the receiver on the indoor unit. See Fig. 25 for
a description of the buttons on the wireless remote.
AUTO
COOL
DRY
1 – MODE SETTING
HEAT
FAN
MODE
3 – ADJUST DOWN
5 – ON/OFF
7 – AIR VERT. SWING
SWING
8 – AIR HORIZ. SWING
SWING
RESET
LOCK C/H
12 – RESET
13 – LOCK
15 – COOL/HEAT
Fig. 25 — Wireless Remote Controller
(40VM900001)
Use a tool to press and hold the LOCK button for at least 10
seconds, then press
to activate. Click
FAN
address and press
to send the setting.
To display an indoor unit address, use a tool to press and
hold the LOCK button for at least 10 seconds, and press
query the addresses.

Non-Programmable Controller (40VM900002)

When setting an address, connect only one wired control-
ler to an indoor unit.
Press ROOM TEMP and SWING simultaneously for 3
seconds. If there is no address for this indoor unit, the display
Indoor unit ad-
TEMP
SET
2 – FAN SPEED SETTING
CLOCK
SET
HOUR
FAN SPEED
4 – ADJUST UP
FAN
6 – AIR DIRECTION
9 – CLOCK SETTING
10 – TIMER ON
AIR DIRECTION
CLOCK
11 – TIMER OFF
TIMER ON
OK
TIMER OFF
14 – OK (CONFIRM)
A40-1734
or
to select an
MODE
shows FE# 00 (see Fig. 26). Otherwise, the display shows the
current address of the indoor unit.
MODE
ROOM TEMP.
FAN
Fig. 26 — Non-Programmable Controller
(40VM900002) IDU Addressing Menu
Click TEMP. UP or TEMP. DOWN to change 00 to the
desired address as shown in Fig. 27. Then press OK to confirm
and exit the setting interface.
to
MODE
ROOM TEMP.
FAN
Fig. 27 — Non-Programmable Controller
(40VM900002) Setting IDU Address
Programmable Controller (40VM900003) —
When setting an address, connect only one wired controller to
an indoor unit.
14
#
TEMP. UP
ON/OFF
TIMER
SWING
OK
TEMP. DOWN
#
TEMP. UP
ON/OFF
TIMER
SWING
OK
TEMP. DOWN