Download Print this page

Rinnai AH083CP Installation And Operation Manual page 14

Hydronic, with/without internal circulation pump

Advertisement

Air Handler
Air Handler
IMPORTANT
• All capacities are based on 70°F entering air temperature.
• For entering air temperatures other than 70°F, use the following capacity correction factors:
(72°F x .982), (68°F x 1.02), (66°F x 1.04)
• Glycol correction factors: (10% X .98), (20% X .95), (30% X .92), (40% X .88)
• Refer to the "Approved Cleaners, Inhibitors and Antifreezes" section (in the Appendix of the "I-Series
Condensing Combi Boiler Installation and Operation Manual") for a complete list of approved glycols.
14
Entering Water
Model
Temperature
120°F
AH083P
140°F*
160°F
120°F
AH084P
140°F*
160°F
120°F
AH125P
140°F*
160°F
120°F
AH166P
140°F*
160°F
120°F
140°F*
AH206P
160°F
Entering Water
Model
Temperature
120°F
AH083P
140°F*
160°F
120°F
AH084P
140°F*
160°F
120°F
AH125P
140°F*
160°F
120°F
AH166P
140°F*
160°F
120°F
AH206P
140°F*
160°F
Blower Speed (Btu/hr)
Low
Medium
21,000
23,000
29,000
32,000*
38,000
42,000
23,000
25,000
32,000
35,000*
41,000
46,000
32,000
33,000
44,000
47,000*
57,000
60,000
41,000
42,000
58,000
60,000
75,000
78,000
41,000
42,000
58,000
60,000
75,000
77,000
Blower Speed (Btu/hr)
Low
Medium
21,000
23,000
29,000
32,000*
38,000
41,000
23,000
25,000
32,000
35,000*
41,000
46,000
32,000
34,000
45,000
47,000*
58,000
61,000
41,000
43,000
58,000
60,000
75,000
78,000
41,000
42,000
58,000
60,000
76,000
77,000
Hydronic Air Handler Installation and Operation Manual
* Bold text
is default
High
setting
25,000
35,000
45,000
27,000
38,000
50,000
35,000
49,000
63,000
44,000
62,000*
80,000
43,000
61,000*
78,000
* Bold text
is default
High
setting
25,000
35,000
45,000
27,000
39,000
50,000
35,000
50,000
64,000
44,000
62,000*
80,000
43,000
61,000*
79,000

Advertisement