Appliance Type
Installation
Suitable for Potable Water Systems
Configurations
Circulation Pump Included
Product Weight - lb. (kg) (approximate)
Cabinet Construction
Nominal CFM (Cubic Feet/Minute)
Nominal Output Btu/hr at 140°F
Rated Voltage
Transformer Size and Type
Blower Wheel (Diameter x Width)
Blower Motor Type
Blower Motor Hot Water Coil Rows
Coil Material
Blower Motor Horsepower (HP)
Blower Full Load Amps (FLA)
Water Connection
Control Board
Certifications
1
Reference tables in sections 3.8.4 and 3.8.5 for specific BTU output.
Rinnai products are continually being updated and improved; therefore, specifications are subject to
change without prior notice.
Hydronic Air Handler Installation and Operation Manual
AH083P
(Internal Circulation Pump Not Included)
Indoor (approved for manufactured housing and mobile homes)
•
Vertical: Upflow with bottom or side (left or right side) return
•
Horizontal: Upflow with bottom return
57 (26)
Embossed cabinet in heavy gauge galvanized steel to prevent
corrosion. Cabinet lined with 5/8 in. foil faced insulation.
800
1
30,000
9x6 in.
3
1/3
5.3
•
Factory Installed
•
Freeze protection activates at 40°F and deactivates at 70°F
•
Thermostat connections
•
60-second time delay for blower activation
•
Boiler activation dry contact
•
24V AC isolation valve control
AH084P
AH125P
Hydronic Air Handler
Yes
No
57 (26)
57 (26)
800
1200
40,000
50,000
120 V, 60 Hz, 1 Ph
40 VA, Class 2
9x6 in.
10x8 in.
3-Speed PSC
4
Copper Coil, UV Resistant Pan
1/3
1/2
5.3
7.1
3/4 in. Sweat
ETL Listed
AH166P
AH206P
62 (28)
74 (34)
1600
2000
60,000
60,000
10x8 in.
10x10 in.
3
3/4
3/4
7.5
10.5
11