Appliance Type
Installation
Suitable for Potable Water Systems
Configurations
Circulation Pump Included
Product Weight - lb. (kg) (approximate)
Cabinet Construction
Nominal CFM (Cubic Feet/Minute)
Nominal Output Btu/hr at 140°F
Rated Voltage
Transformer Size and Type
Blower Wheel (Diameter x Width)
Blower Motor Type
Blower Motor Hot Water Coil Rows
Coil Material
Blower Motor Horsepower (HP)
Blower Full Load Amps (FLA)
Water Connection
Control Board
Certifications
1
Reference tables in sections 3.8.4 and 3.8.5 for specific BTU output.
Rinnai products are continually being updated and improved; therefore, specifications are subject to
change without prior notice.
Hydronic Air Handler Installation and Operation Manual
AH083P
(Internal Circulation Pump Not Included)
Indoor (approved for manufactured housing and mobile homes)
Vertical: Upflow with bottom or side (left or right side) return
Horizontal: Upflow with bottom return
57 (26)
Embossed cabinet in heavy gauge galvanized steel to prevent
corrosion. Cabinet lined with 5/8 in. foil faced insulation.
800
1
30,000
9x6 in.
3
1/3
5.3
Factory Installed
Freeze protection activates at 40°F and deactivates at 70°F
Thermostat connections
60-second time delay for blower activation
Boiler activation dry contact
24V AC isolation valve control
AH084P
AH125P
Hydronic Air Handler
Yes
No
57 (26)
57 (26)
800
1200
40,000
50,000
120 V, 60 Hz, 1 Ph
40 VA, Class 2
9x6 in.
10x8 in.
3-Speed PSC
4
Copper Coil, UV Resistant Pan
1/3
1/2
5.3
7.1
3/4 in. Sweat
ETL Listed
AH166P
AH206P
62 (28)
74 (34)
1600
2000
60,000
60,000
10x8 in.
10x10 in.
3
3/4
3/4
7.5
10.5
11