Specifications Ratings - Omron E5CD-800 Manual

Digital simple type
Table of Contents

Advertisement

E5ED-800
Specifications
Ratings
Power supply voltage
Operating voltage range
Power consumption
Sensor input
Input impedance
Control method
Relay output
Control
Voltage output
output
(for driving
SSR)
Number of
outputs
Auxiliary
output
Output
specifications
Number of
inputs
Event
External
input
contact input
specifications
Setting method
Indication method
Multi SP
Bank switching
Other functions
Ambient operating
temperature
Ambient operating
humidity
Storage temperature
Altitude
Recommended fuse
Installation environment
22
A in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
Models with option selection of 800: 6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max.
at 24 VDC
All other models: 8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 Ω max., Voltage input: 1 MΩ min.
(Use a 1:1 connection when connecting the ES2-HB/THB.)
ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V, 10 mA
(reference value)
Output voltage: 12 VDC ±20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
2
SPST-NO relay outputs, 250 VAC, 2 A (resistive load)
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference values)
2
Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
Digital setting using front panel keys
11-segment digital display, individual indicators, and bar display
Character height: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm
Three displays Contents: PV/SV/MV, PV/SV/Multi-SP, PV/SV/Remaining soak time, etc.
Numbers of digits: 4 digits each for PV, SV, and MV displays
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or serial
communications.
None
Adaptive control, automatic filter adjustment, water-cooling output adjustment, indication data (power ON time
monitor, ambient temperature monitor, and control output ON/OFF count monitors), parameter masking, operation
after power ON, manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions,
heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter,
robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change rate limit, logic
operations, temperature status display, simple programming, moving average of input value, and display
brightness setting
−10 to 55°C (with no condensation or icing),
For 3-year warranty: −10 to 50°C with standard mounting (with no condensation or icing)
25% to 85%
−25 to 65°C (with no condensation or icing)
2,000 m max.
T2A, 250 VAC, time-lag, low-breaking capacity
Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1)