Honeywell Krom Schroder BCU 580 Technical Information page 72

Burner control unit
Table of Contents

Advertisement

Parameters
Parameter 09 = 4: max. 5 × in 15 min. for burner 1. The
restart function is active and is also monitored. In cer-
tain conditions, it is possible that the restart function is
repeated continuously without a safety shut-down with
subsequent fault lock-out being performed. The BCU
has a safety shut-down with subsequent fault lock-out
option if more than 5 restarts are performed within a
period of 15 minutes.
Taking into account national standards and require-
ments, it must be clarified whether the option may be
used .
Parameter 09 = 5: max. 5 × in 15 min. for burner 2.
Parameter 09 = 6: max. 5 × in 15 min. for burner 1 and 2.
BCU 580 · Edition 11.15l
72