Safety Time 2 T; Sa2; Flame Proving Period 2 T Fs2 - Honeywell Krom Schroder BCU 580 Technical Information

Burner control unit
Table of Contents

Advertisement

Parameters

10 .3 .6 Safety time 2 t

Parameter 96
During the safety time 2 t
(main flame) is ignited. It can be set to 2, 3, 5 or 10 s.
00
02
03
04
t
t
Z
FS1
t
SA1
Safety time 2 starts with the application of the ϑ2 sig-
nal (terminal 4). Valve V2 opens at the start of safety
time 2. The fuel supply to burner 2 is released so that
a flame can form. If no flame is detected at the end of
safety time 2, the valves are closed again. Depending
on parameter 08 (Burner 2 start-up attempts), the BCU
reacts either with an immediate safety shut-down with
fault lock-out (P08 = 1) or with one or two additional
start-up attempts (P08 = 2 or 3). The BCU will complete
a maximum of three start-up attempts.
Safety time 2 must be determined on the basis of cur-
rent national standards and regulations. The burner ap-
plication and the burner capacity are the main criteria
for this.
BCU 580 · Edition 11.15l

SA2

, the flame on burner 2
SA2
06
07
08
t
t
SA2
FS2
If the ϑ1 signal (terminal 1) drops out during safety
time 2, the valves will not be switched off until the end
of safety time 2.
10 .3 . 7 Flame proving period 2 t
Parameter 97
88
11
L1
46
Flame proving period 2 t
1
ϑ1
9
to enable the flame on burner 2 to stabilize after the
13
V1
elapse of safety time 2. Only when the flame proving
57
V4
5
1
period has elapsed will the next program steps be initi-
4
ϑ2
14
V2
ated by the BCU. The flame proving period can be set
8
2
41
between 0 and 20 s.
42
1
43
2
17-18
00
02
t
t
Z
t
SA1
FS2
can be parameterized
FS2
03
04
06
07
t
t
t
FS1
SA2
FS2
88
08
11
L1
46
1
ϑ1
9
13
V1
57
V4
5
1
4
ϑ2
14
V2
8
2
41
42
1
43
2
17-18
t
69